JV376VWW - GE High Performance Range Hood

GE Appliances

Specification Revised 4/00

For answers to your Monogram,

®

GE Profile Performance Series,

GE Profile

or GE appliance questions, call

GE Answer Center

®

service, 800.626.2000.

R

Listed by
Underwriters
Laboratories

Ductwork Requirements

Use 3-1/4” x 10” or 7” round ducting for the best performance.
The length of ductwork and number of elbows should be kept
to a minimum for efficient operation.

Use caulking to seal exterior openings around the hood.

Static Pressure vs Duct Length
Equivalent Duct Length (ft.)

Static

Rect.

Pressure

CFM

3-1/4” x 10”

7” dia.

8” dia.

9” dia.

.06

4

10

19

34

.10

410

7

17

31

56

.15

400

11

25

47

83

.20

370

15

33

62

111

.25

345

18

42

78

90° elbow

5

11

12

14

45° elbow

2-1/2

5-1/2

6

7

10

Equivalent length in feet

Air volume in CFM

20

30

40

50

0

0

100

200

300

400

500

7" RND

3-1/4" x 10"

3-1/4" x 10" Transition to 7" Round = 2 ft.
7" Round elbow = 8 ft.
7" Roof cap = 70 ft.

Ducting Chart

Venting

This hood must be vented vertically through upper cabinets or horizontally
through an outside wall. Ductwork is not included.
Improper duct sizing or restrictive roof caps reduce air moving capacity
and will not provide enough ventilation for an indoor electric grill.
Indoor electric grills produce more smoke than normal cooking and require
at least 410 CFM to provide adequate ventilation.
Follow the guidelines for proper duct sizing in the duct charts. NOTE: The
venting system must exhaust to the outside.