Installing the water heater, Branch circuit sizing and wire size guide, Electrical connections – GE AP12170-4 User Manual

Page 8: Condensation

Advertising
background image

8

Installing the water heater.

CAUTION: The presence of water in the piping and water heater does not provide sufficient conduction for a

ground. Non-metallic piping, dielectric unions, flexible connectors etc. can cause the water heater to be electrically
isolated.

Customer Service

T

roubleshooting Tips

Care and Cleaning

Operating Instructions

Installation Instructions

Safety Instructions

Branch Circuit Sizing and Wire Size Guide

Total Water

Recommended Over Current Protection

Copper Wire Size AWG Based

Heater Wattage

(fuse or circuit breaker amperage rating)

on N.E.C. Table 310-16 (75°C)

120V

208V

240V

120V

208V

240V

1500*

20

15

15

12

14

14

1700

20

15

15

12

14

14

2000

25

15

15

10

14

14

2500

30

15

15

10

14

14

3000

35

20

20

8

12

12

3500

25

20

10

12

3800

25

20

10

12

4000

25

25

10

10

4500

30

25

10

10

5000

30

30

10

10

5500

35

30

8

10

6000

40

35

8

8

9000

50

8

*Less than 1500 watts may be wired 14 gauge with 15 amp protection. Check Local Electrical Codes, as they will also apply.

Electrical Connections

A separate branch circuit with copper
conductors, overcurrent protective device
and suitable disconnecting means must
be provided by a qualified electrician.
All wiring must conform to local codes
or latest edition of National Electrical
Code ANSI/NFPA 70.
The water heater is completely wired to
the junction box inside jacket at the top
front of the water heater. An opening for
1/2

or 3/4electrical fitting is provided

for field wiring connections.
The voltage requirements and wattage load
for the water heater are specified on the
rating plate on the front of the water heater.

The branch circuit wiring should
include either:

Metallic conduit or metallic sheathed
cable approved for use as a grounding
conductor and installed with
fittings approved for the purpose.
Non-metallic sheathed cable, metallic
conduit or metallic sheathed cable
not approved for use as a ground
conductor shall include a separate
conductor for grounding. It should
be attached to the ground terminals
of the water heater and the electrical
distribution box.

WARNING

WARNIN

G

Water heater junction box.

NOTICE: This guide
recommends minimum
branch circuit sizing and
wire size based on National
Electric Code. Refer to
wiring diagrams in this
manual for field wiring
connections.

Ground screw

Junction

box

cover

Wire connections

Conduit

connector

Condensation

Condensation can form on the tank
when it is first filled with water.
Condensation might also occur with
a heavy water draw and very cold inlet
water temperatures.

This condition is not unusual, and will
disappear after the water becomes
heated. If, however, the condensation
continues, examine the piping and fittings
for possible leaks.

Additional information on this subject
may be found at

www.rheem.com

under “Library,” scroll down to the
Technical Service Bulletins 1400 Series
Section and choose Bulletin #1402.

Advertising
This manual is related to the following products: