Installation instructions, Exhausting the dryer warning – GE PCVH480EK User Manual

Page 17

Advertising
background image

Installation Instructions

17

EXHAUSTING THE DRYER

WARNING –

To reduce the

risk of fire or personal injury:

This clothes dryer must be exhausted to the outdoors.
• Use only 4

″ rigid metal ducting for the home exhaust

duct.

• Use only 4

″ rigid metal or UL-listed flexible metal

(semi-rigid or foil-type) duct to connect the dryer to
the home exhaust duct. It must be installed in
accordance with the instructions found in “Connecting
the Dryer to House Vent” on page 18 of this manual.

• Do not terminate exhaust in a chimney, a wall, a

ceiling, gas vent, crawl space, attic, under an enclosed
floor, or in any other concealed space of a building.

• Never terminate the exhaust into a common duct with

a kitchen exhaust system. A combination of grease
and lint create a potential fire hazard.

• Do not use duct longer than specified in the exhaust

length table. Longer ducts can accumulate lint,
creating a potential fire hazard.

• Never install a screen in or over the exhaust duct.

This will cause lint to accumulate, creating a potential
fire hazard.

• Do not assemble ductwork with any fasteners that

extend into the duct. These fasteners can accumulate
lint, creating a potential fire hazard.

• Do not obstruct incoming or exhausted air.
• Provide an access for inspection and cleaning of the

exhaust system, especially at turns and joints.
Exhaust system shall be inspected and cleaned at
least once a year.

This dryer comes ready for rear exhausting. If space

is limited, use the instructions on pages 21–23 to
exhaust directly from the sides or bottom of the
cabinet.

TOOLS AND MATERIALS YOU WILL
NEED TO INSTALL EXHAUST DUCT

❒ Phillips-head screwdriver

❒ Duct tape or duct clamp

❒ Rigid or UL-listed flexible

metal 4

″ (10.2 cm) duct

❒ Vent hood

❒ Drill with 1/8″ drill bit

(for bottom venting)

❒ Hacksaw

EXHAUST SYSTEM CHECKLIST

HOOD OR WALL CAP

Terminate in a manner to prevent back drafts

or entry of birds or other wildlife.

Termination should present minimal resistance

to the exhaust airflow and should require little
or no maintenance to prevent clogging.

Never install a screen in or over the exhaust

duct.

Wall caps must be installed at least 12

″ above

ground level or any other obstruction with the
opening pointed down.

SEPARATION OF TURNS

For best performance, separate all turns by

at least 4 ft. of straight duct, including distance
between last turn and dampened wall cap.
For turns less than 4 ft. apart, see the Ducting
Component Equivalency Chart.

SEALING OF JOINTS

All joints should be tight to avoid leaks. The male

end of each section of duct must point away
from the dryer.

Do not assemble the ductwork with fasteners

that extend into the duct. They will serve as
a collection point for lint.

Duct joints should be made air- and

moisture-tight by wrapping the overlapped
joints with duct tape or aluminum tape.

Horizontal runs should slope down towards

outdoors 1/4

″ per foot.

INSULATION

Ductwork that runs through an unheated area

or is near air conditioning should be insulated
to reduce condensation and lint buildup.

Advertising
This manual is related to the following products: