Greenheck Fan Greenheck 474750 User Manual

Page 2

Advertising
background image

2

Digital Temperature Interlock

Table of Contents

Product Specification . . . . . . . . . . . . . . . . . . . . . . . . 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . 2
Installation
Hood

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . 2-3

Duct Collar Mounting . . . . . . . . . . . . . . . . . . . . . . 3

Electrical Connections
Sensor

Connections

. . . . . . . . . . . . . . . . . . . . . . . 3

Switch Connections to Control Box

or Fan Control Center . . . . . . . . . . . . . . . . . . . . 3

Circuit

Connections

. . . . . . . . . . . . . . . . . . . . . . . 3

Calibration

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Factory Selected Parameters

Setting Parameters . . . . . . . . . . . . . . . . . . . . 3-4

Control Circuit Diagrams . . . . . . . . . . . . . . . . . . . . 5-6
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Frequently Asked Questions . . . . . . . . . . . . . . . . . . . 8
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Codes and Standards Compliance . . . . . . . . . . . . . . 8
Our Commitment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Receiving and Handling

Upon receiving the equipment, check for both obvious
and hidden damage. Check to be sure that all parts of
the shipment, including accessories, are accounted for.
Make sure the equipment does not suffer any heavy
vibrations or knocks.

Storage

If a temperature interlock must be stored prior to
installation, it must be protected from dirt and moisture.
Indoor storage is recommended. For outdoor storage,
cover the control package with a tarp to keep it clean,
dry, and protected from UV (ultraviolet) radiation
damage.

Improper storage which results in damage to the unit
will void the warranty.

NOTE

Resistive temperature detector(s) may be factory
installed. If so, continue to the next section.

Resistive Temperature Detector(s)
Hood Mounting

Installation

Control Box Mounting

Locate an area with enough space to mount the control
box and fasten to the wall. Avoid installing the control
box in environments with high magnetic and/or radio
frequency interference.

2. Cut a 3/4 to 7/8-inch diameter

hole in the flat spot of the
capture tank. Make
sure the resistive
temperature detector(s)
will not interfere with fire
system nozzles and is
not within 12 inches of
light fixtures.

0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole

Hood Surface

NOTE

Control box may be factory mounted. If so, continue
to the next section.

1. Locate flat area(s) at the top interior of the hood in

front of the filters, towards the front of the hood.

3 inch air space

2 inch typical

19.525 inches

Sensor Install

(cutout area)

Exhaust Area

Supply Area

(optional)

P.O.BOX 410 SCHOFIELD, WI

TITLE

INSTR, ADJ. T

Top View of Exhaust Hood

Octagon Extension
PN 830125

Lock Washer

Nut

Compression Seal
PN 463570

Gasket

J-Box Plate
PN 732396

3. Place the J-box plate inside of the octagon extension

ring and place over the hole.

4. Disassemble the compression seal and place

through hole and J-box plate as shown. Tighten the
nut inside the octagon extension ring.

®