4

Digital Temperature Interlock

Calibration

The temperature controller is preset by the factory to
turn the fans on at 95°F. This is controlled by the set
point on the temperature controller. The temperature set
point may have to be adjusted slightly depending on
both ambient and cooking conditions. The adjustment is
made through the buttons on the temperature controller.
The controller is capable of monitoring two separate
sensors. If more than one sensor is utilized with a single
controller, two set points can be adjusted. To adjust,
follow these instructions:

1. If setting set point 1 (St1), press Set. The display

shows St1 and then the current value of St1.

If setting set point 2 (St2), press Set twice, slowly.
The display shows St2 and then the current value of
St2.

2. Press the

S or T to change the set point.

3. Press Set to confirm the new value of either St1 or

St2.

4. Check system operation before making additional

adjustments.

Factory Selected Parameters

The factory will pre-program the controllers to be
properly integrated into the control panel. Except for
the set points, the other parameters should never need
adjusting. However, there are three different types of
parameters that are accessible on the controller. Access
differs depending on the type: set point; frequently used
parameters (P); and configuration parameters (c, d, F).

Setting type P parameters

Type P parameters (frequents) are indicated by a code
beginning with the letter P, followed by one or two
numbers.

1. Hold the

Prg

mute

button, after 3 seconds the displays

shows the firmware revision code (e.g. r2.1) is
shown, after 5 seconds (in the event of alarms, first
the buzzer is muted) the code of the first type P
modifiable parameter, P1.

2. Press

S or T until reaching the desired parameter.

3. Press Set to display the associated value.

4. Increase or decrease the value using

S or T

respectively, until reaching the desired value.

5. Press Set to temporarily save the new value and

return to the display of the parameter code.

6. Repeat operations from 4 to 5 to set other

parameters.

7. To permanently save the new values of the

parameters, press

Prg

mute

for 5 seconds, thus exiting

the parameter setting procedure.

Setting type c, d, F parameters

Type c, d or F (configuration) parameters are indicated
by a code beginning with letters c, d, F respectively,
followed by one or two numbers.

1. Press

Prg

mute

and Set together for more than 5

seconds. The display shows the number 0.

2. Press

S or T until displaying the password: 77

3. Confirm by pressing Set

4. If the value entered is correct, the first modifiable

parameter c0 will be shown, otherwise the standard
display will resume.

5. Press

S or T until reaching the parameter to be

modified.

6. Press Set to display the associated value.

7. Increase or decrease the value using

S or T

respectively, until reaching the desired value.

8. Press Set to temporarily save the new value and

return to the display of the parameter code.

9. Repeat operations from 5 to 8 to set other

parameters.

10. To permanently save the new values of the

parameters, press

Prg

mute

for 5 seconds, thus exiting

the parameter setting procedure.

Factory Selected Parameters

Parameter

Description

Factory Setting

St1

Set Point 1

95

St2

Set Point 2

95

c0

Operating Mode

1

P1

Set Point Differential

5.0

P2

Set Point Differential

5.0

P3

Dead Zone Differential

0

c6

Delay between two outputs

0

c9

Minimum relay on time

5

c10

Probe alarm output status 1

1

d10

Probe alarm output status 2

1

c11

Output Rotation

4

c13

Probe Type

3

P14

Probe 1 Calibration

0

P15

Probe 2 Calibration

0

c18

Unit of Measure

1

c19*

Function of probe 2

0 or 7

*Parameter c19 is factory set at 0. If controller is connected to two
sensors, then the parameter is factory set at 7..

NOTE

The controller is pre-programed at the factory to
operate with the digital temperature interlock
components. No further parameter changes should
be necessary.

Displaying the Inputs

1. Press

T. The current input will be displayed,

alternating with the value:

b1 : probe1
b2 : probe 2
di1 : digital input 1
di2 : digital input 2
St1 : set point 1
St2 : set point 2

2. Press

S or T to select the input to be displayed.

3. Press Set for three seconds to confirm.

®