Electrical connections, Sensor connections, Circuit connections – Greenheck Fan Greenheck 474750 User Manual

Page 3

Advertising
background image

3

Digital Temperature Interlock

Resistive Temperature Detector(s)
Duct Collar Mounting

1. Locate the exhaust duct on top of the hood. A 3/4 to

7/8-inch

(19.0 to 22.2 mm)

diameter hole must be cut

into the duct 2 inches

(50.8 mm)

above the

hood top. Center the
hole along the side
of the duct. Make
sure that the resistive
temperature detector
will not interfere with
any fire system nozzles, or other items installed in
the exhaust duct. If an exhaust fire damper is present
the hood exhaust collar, it must be removed prior to
temperature sensor installation.

2. Place the J-box plate inside of the octagon extension

ring and place over the hole in the exhaust collar.

3. Disassemble the

compression
seal and place
through hole in
duct collar and
J-box plate as
shown. Tighten
the nut inside
the octagon
extension ring.

4. Place the

resistive
temperature
detector
through the
compression
seal and
tighten the
compression
fitting.

5. Refer to Electrical Connections section for

instructions on wiring the temperature sensor.

6. Install the cover for the octagon box.

NOTE

All field installation and wiring of electrical equipment
must be done to meet NEC and local codes.

5. Place the resistive

temperature
detector through
the compression
seal and tighten
the compression
fitting.

6. Refer to Electrical

Connections
section for
instructions on wiring the temperature sensor.

7. Install the cover for the octagon box.

Resistive Temperature
Detector (RTD)
PN 384925

Octagon Cover
PN 380926

Octagon Extension
PN 830125

2 inches
(50.8 mm)

Hood Exhaust Collar
Front Side

0.75 to 0.875 inch
(19.0 to 22.2 mm)
diameter hole

Octagon Extension
PN 830125

Lock Washer

Nut

1/4-inch Compression Seal
PN 463570

J-Box Plate
PN 732396

Quik Seal
Gasket

Resistive Thermostat
Detector (RTD)
PN 384925

Octagon Cover
PN 380926

Octagon Extension
PN 830125

Electrical Connections

Sensor Connections

1. Run two 18 awg stranded thermostat wires from

each temperature sensor to the appropriate electrical
circuit connections. (See Step 3 for connection
options).

2. In junction box, connect leads on RTD to the 18 awg

conductors using appropriate size wire nuts.

• Wires are interchangeable with one another.

3.

Choose
the final
connection
option
based on:

CAUTION

Do not connect temperature sensor in series with fan
power. This will result in damage to the temperature
sensor and will require replacement.

NOTE

Separate as much as possible the probe and digital
input cables from inductive loads and power cables,
to avoid any electromagnetic disturbance. Never lay
power and probe cables in the same cable conduits
(including those for the electrical panel). Loosen
every screw and insert the cable end, next tighten
the screws and gently pull the cables to check their
tightness.

Switch Connections to Control Box or
Fan Control Center

Connect a Single Pole Single Throw (SPST) switch
to terminals S1H and S1. This is the same whether
temperature interlock is in a separate control box or
integrated in a kitchen fan control center.

Circuit Connections

1. Standard Interlock Control

120VAC, 10 or 15 amp circuit to terminals
H1 and N1

120VAC, 24VAC or other control circuit for fan
starter activation (factory separated from main
power connection shown in previous bullet)

- Control circuit power to terminal CP1

- Terminal CP2 to fan starter coils (hot)

2. Kitchen Fan Control Center Integration (KFCC)

120VAC, 15 amp circuit to H1 and N1 in fan
control center

- No additional control circuits are required

- Fan starters are factory-wired.

Sensor

Terminals

First Sensor

T1-A and T1-B

Others

(if applicable)

T2-A and T2-B
T3-A and T3-B
T4-A and T4-B
T5-A and T5-B
T6-A and T6-B
T7-A and T7-B
T8-A and T8-B
T9-A and T9-B
T10-A and T10-B
T11-A and T11-B
T12-A and T12-B

®

Advertising