Frequently Asked Questions

What temperature is the temperature controller set
to from the factory?
95º

Fahrenheit.

Will the temperature interlock automatically start/
stop the fans?

When connected properly to fan starters the
temperature interlock will automatically control
the fans without input from the user. However, the
intended use of the temperature interlock is as back-
up to manual control.

May I connect the power going to my fan directly
through the control box?

No, the control box should only use control voltage
only (24-120V), and a separate 120V power source
is required to run the temperature interlock controls.
Greenheck recommends the use of starters sized for
each fan.

Can I use one control box for multiple hood systems?

This can be done, however, it is not recommended.
Any one of the temperature controllers would turn on
all hoods running on that control box. It is better to
have one hood/fan per control box, plus a significant
energy savings can be obtained if one or more of the
hoods is not in operation.

Can I still turn my fan on and off?
Yes, the temperature interlock is designed to be

operated with a typical on/off switch. The fan may not
turn off directly after turning the fan switch off, it will
sense when the cooking operations have cooled and
then turn off.

Replacement Parts

Part

Number

Description

384925

Temperature Sensor (RTD)
MAMAC TE-700-0-3-A

384920

Temperature Controller
CAREL iR33-DN33 DN33W7HR20

830125

Extension, Octagon (drilled)
SC55151-1/2 (380928)

732396

J-Box Plate

380926

Cover, Octagon Box
SC#54-C-1RACO 722

384905

Terminal Block, Single Pole,
DIN-RAIL MT, ABB ZS6

384908

Jumper, DIN-RAIL
Terminal Block Two Pole ABB JB6-2

463570

Evergreen Compression Seal
1/4-inch, #302

Codes and Standards Compliance

• UL

710

• National Fire Protection Association (NFPA 96)

• International Mechanical Code (IMC) 2006

Section 507.2.1.1

8

474750 • Digital Temperature Interlock, Rev. 3, November 2012

Copyright 2012 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the
Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment

AMCA Publication 410-96, Safety Practices for Users and Installers of Industrial and Commercial Fans, provides additional safety
information. This publication can be obtained from AMCA International, Inc. at www.amca.org.

Advertising