Installation, Remote power off communication port 3 – MGE UPS Systems Comet EX 11 RT 3:1 User Manual

Page 17

Advertising
background image

34007724EN/AA

- Page 17

BY

PASS

NORMAL

Card Settings

RS232 Download

66074

UPS
data

Reset

100 10

1 2
ON

ETHERNET

RS232

IP=
MAC=00E0D8FF855E

Installation of communication cards (optional, standard with the Network Pack version)

It is not necessary to shut down the UPS to
install the communication card:

1 - Remove the slot cover secured by two
screws.

2 - Insert the card 1 into the slot.

3 - Secure the card with both screws.

Communication card.

1

2. Installation

Signal:

- activation voltage: 5 V DC to 27 V DC.
- current: 10 mA max.

Remote Power Off communication port 3

5 V DC to 27 V DC

Used in conjunction with the optional EPO battery module, this port enables total isolation of all power sources connected
to the UPS in case of emergency (the cable is not provided).

Remote power off contact normally open

Remote power off contact normally closed

5 V DC to 27 V DC

RJ11

5 4 3 2 1

6

5 4 3 2 1

6

RJ11