5. Appendices

5.1 Technical specifications

Electrical characteristics

I/T network and industrial operating modes

Bypass AC
Normal AC

Bypass AC

Normal AC

Upstream
circuit breaker
(not supplied)

Downstream
circuit breaker
(not supplied)

Input
fuse

Output
fuse

Upstream
circuit breaker
(not supplied)

Downstream
circuit breaker
(not supplied)

Input
fuse

Output
fuse

Upstream
circuit breaker
(not supplied)

Selection of protection devices

UPS unit with common Normal and Bypass AC inputs

Overload, and Bypass

AC source in tolerance.

Overload, and Bypass

AC source not in tolerance.

Output short circuit and

Bypass AC source in

tolerance.

Output short circuit and

Bypass AC source not in

tolerance.

I/T network mode

Load is transfered to Bypass AC source.

UPS returns to normal mode if overload released.

The UPS shuts down and load is not transfered to

Bypass AC source.

The load remains powered by the UPS.

The UPS shuts down after 3 minutes if the short

circuit remains.

The load remains powered by the UPS. The UPS

shuts down after 3 minutes if the short circuit

remains.

Industrial mode

Same as I/T network mode, but the UPS does not

return to normal mode if overload released.

Load is transfered to Bypass AC source with 10

milliseconds output break. The UPS does not return to

normal mode if overload released.

Load is transfered to Bypass AC source, the UPS

returns to normal mode if the short circuit is released

by downstream circuit breaker action (see section 2.6).

The load is transfered to Bypass AC source with 10

milliseconds output break. The UPS does not return to

normal mode if the short circuit is released by

downstream circuit breaker action (see section 2.6).

UPS unit with separate Normal and Bypass AC inputs

When sizing the upstream circuit breakers, the parameters presented below must be taken into account:

Line current values

Continuous current

at 400/320 Volts and

nominal load

9/10 A

10/11 A

15/19 A

UPS

power rating

5 kVA

7 kVA

11 kVA

Continuous current at 320 Volts

and overload = 110 %

limited to 2 minutes

11 A

12 A

21 A

Input fuse rating

25 A

25 A

30 A

Output fuse rating

80 A

80 A

100 A

Discrimination of upstream/downstream protections mentioned in paragraph 2.6 is achieved for a 30 m cable length and
10 mm

2

cross section.

Circuit breaker capacity must be selected according to the installation, length and cross section of cables.

Normal AC
source circuit
breaker

Normal AC
source circuit
breaker