34007724EN/AA

- Page 25

BY

PASS

NORMAL

_

+

N

L

BATTERY

AC INPUT

2. Installation

Connection of CLA module

AC Input

To battery

29

28

Connect the battery cable 28 (provided with the CLA module) between the power module and the CLA module.

Connect the cable 29 (provided with the CLA module) between the power module and the CLA module.

Connect the battery:

Cable cross-section (not provided): 10 mm

2

, solid or stranded wire (maximum 13 mm

2

or AWG 6).

Use a circuit-breaker (curve B, 50 A) for cable protection.

Connect the input cable of the CLA module to the AC input:

AC input cable cross-section (not provided) : 2,5 mm

2

.

Use a circuit-breaker (curve C, 10 A) for cable protection.