Presentation – MGE UPS Systems Comet EX 11 RT 3:1 User Manual

Page 9

Advertising
background image

34007724EN/AA

- Page 9

1. Presentation

Battery extensions for UPS backup times up to 60 minutes (at full load)

Comet EX RT offers a standard backup time of 5/9 minutes at full load.
To increase backup time, it is possible to connect Comet EXB 7 RT / EXB 11 RT modules to the UPSs.

Battery extensions for Comet EX 5 RT, Comet EX 7 RT or Comet EX 11 RT

CLA module (Long backup time charger) for backup times from 2 to 8 hours
(Part number 68004)

Very long backup times, from 2 to 8 hours at full load, require a Comet EX RT CLA module.

+

+

+

Comet EX 5/7 RT
+ EXB 7 RT

/

Comet EX 11 RT
+ EXB 11 RT

Comet
EXB 7 RT

/

Comet
EXB 11 RT

7 kVA:

11 kVA:

7 min

5 min

20 min

14 min

32 min

22 min

+

+

45 min

30 min

57 min

42 min

70 min

53 min

Comet
EXB 7 RT

/

Comet
EXB 11 RT

Comet
EXB 7 RT

/

Comet
EXB 11 RT

Comet
EXB 7 RT

/

Comet
EXB 11 RT

Comet
EXB 7 RT

/

Comet
EXB 11 RT

5 kVA:

9 min

26 min

42 min

60 min

72 min

87 min

2 hours

4 hours

8 hours

50 Ah

100 Ah

200 Ah

65 Ah

130 Ah

260 Ah

Total battery voltage : 240 V DC (20 x 12V DC).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalisation section).

100 Ah

200 Ah

400 Ah

Comet EX7 RT

Recommended batteries for:
Comet EX5 RT

Battery backup time

Comet EX11 RT

Comet
EX 5 RT /
EX 7 RT /
EX 11 RT

Comet
EX RT CLA

~

50A

BY

PASS

NORMAL

Advertising
This manual is related to the following products: