Minuteman UPS MCP-E User Manual

Page 10

Advertising
background image

9

NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker
which will provide for an emergency power off.

(Must be performed by Authorized

Service Personnel ONLY)

Model

MCP 5000iE

MCP7000iE

Input Circuit Breaker

40 Amp

50 Amp

Input Wire Size/Temp 8 AWG/min75

°

C 6 AWG/min75

°

C

Wire Conductor

Three conductor, copper wire only

Tightening torque for
pressure wire connectors
having screws

Block diagram of the MCP 5000iE and MCP 7000iE input and output wiring.

English

Torque 17.6Lbs (8kg)

Advertising