Configurable parameters and settings, Englishenglish – Minuteman UPS MCP-E User Manual

Page 27

Advertising
background image

26

(These items may require optional software or hardware)

FUNCTION

FACTORY DEFAULT

DESCRIPTION

USER CHOICES

EnglishEnglish

CONFIGURABLE PARAMETERS

AND SETTINGS

UPS ID

MCP-E SERIES

Up to 64 characters to

define the UPS

Use this function to uniquely identify the

UPS in your network configuration

Battery installation date

Date of Manufacture

Date of Battery Replacement-

day/month/year (xx/xx/xxxx)

Enter the current date when

replacing the batteries

Battery life in days

Preset for 1826 days

Enter up to 5 characters

When replacing the batteries,

calculate the actual number of days in

use after manufacture date and then

enter this expected life for your

environment

Auto Restart:

Enable/Disable

Enabled

User may Enable or

Disable Autorestart

When "enabled", the UPS will

automatically restart and operate in

normal AC mode after a low battery

shutdown and normal AC has returned

Set audible

alarm state

Enabled

User may Enable or Disable

until Low Battery Warning

Enabled: The UPS will emit an

audible alarm every 10 seconds

when in the battery mode.

Disabled until Low Battery Warning:

Used when software is controlling the

UPS or to silence the alarm. In
this state, the UPS will not emit

an audible alarm until the unit

reaches low battery warning level.

Enable or Disable all

UPS functions

Disabled

User is required to enable prior

to operation. The UPS will not

operate until enabled.

This is a safety feature to prevent

operation while packaged during

shipping.

Set Inverter Output

Voltage

120 vac on 120 volt units.
230 vac on 230 volt units.

120 volt units: 100,110,115,120

230 volt units: 220,230,240

Allows the customer to set the voltage

based on the environment in which the

unit will be installed. This voltage is

set via external dip switch. The dip

switch is on the rear panel of the unit.