General information – Multiquip MQ MultiQuip Power DCA85USJ2 User Manual

Page 16

Advertising
background image

PAGE 16 — DCA85USJ2 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #1 (03/22/11)

GENERATOR

This generator (Figure 3) is a high quality portable (requires
a trailer for transport) power source for telecom sites,
lighting facilities, power tools, submersible pumps and other
industrial and construction machinery.

ENGINE OPERATING PANEL

The “Engine Operating Panel” is provided with the following:

 Tachometer

 Water Temperature Gauge

 Oil Pressure Gauge

 Charging Ammeter Gauge

 Fuel Level Gauge

 Panel Light/Panel Light Switch

 ECU Controller

 Engine Speed Switch

 Emergency Stop Lamp

 Warning Lamp

 Pre-Heat Lamp

 Fuel Leak Detected Alarm Lamp

 Diagnostic Gauge

GENERATOR CONTROL PANEL

The “Generator Control Panel” is provided with the following:

 Frequency Meter (Hz)

 AC Ammeter (Amps)

 AC Voltmeter (Volts)

 Ammeter Change-Over Switch

 Voltmeter Change-Over Switch

 Voltage Regulator

 3-Pole, 250 amp Main Circuit Breaker

 “Control Box” (located behind the Gen. Control Panel)

• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Selector Switch

OUTPUT TERMINAL PANEL

The “Output Terminal Panel” is provided with the following:

 Three 120/240V output receptacles (CS-6369), 50A

 Three auxiliary circuit breakers, 50A

 Two 120V output receptacles (GFCI), 20A

 Two GFCI circuit breakers, 20A

 Five output terminal lugs (3Ø power)

OPEN DELTA EXCITATION SYSTEM

This generator is equipped with the state of the art “Open-
Delta”
excitation system. The open delta system consist
of an electrically independent winding wound among
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectifi ed and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the confi guration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fi xed ceiling” and responds
according the demands of the required load.

ENGINE

This generator unit incorporates an John Deere 6068HF285
diesel engine. This engine is designed to meet every
performance requirement for the generator. Reference
Table 2 for engine specifi cations.

In keeping with MQ Power’s policy of constantly improving
its products, the specifi cations quoted herein are subject
to change without prior notice.

ELECTRIC GOVERNOR SYSTEM

The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.

EXTENSION CABLES

When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 6) as a
guide for selecting proper extension cable size.

GENERAL INFORMATION

Advertising
This manual is related to the following products: