OUTSIDE COMBUSTION AIR PRECAUTIONS AND RECOMMENDATIONS

Note: The use of outside air for combustion
is optional unless required by building
codes. It is only necessary to supply
outside combustion air to one side of
fireplace. Use model OAC4 combustion
air kit (see page 17).

1. Avoid extremely long runs and numerous

turns in duct leading from fireplace to combus-

tion air assembly. These conditions increase

the resistance to free flow of air through duct.

See Figures 11 and 12.

2. Locate combustion air assembly at an exterior

location. Make sure the location cannot be

accidentally blocked. Locate assembly above

snow line to prevent snow from blocking

assembly.

3. Never mount combustion air inlet assembly

in garage or storage area where combus-

tible fumes (gasoline) might be drawn into

fireplace.

4. Combustion air may be drawn from crawl

space under house when adequate supply

of air is provided by open ventilation. See

Figure 11.

Note: Never take combustion air from attic
space or garage space.

Note: Install outside combustion air ONLY
ON LEFT-HAND SIDE of fireplace.

Figure 11 - Installing Unit Above Basement or Crawl Space

Figure 12 - Installing Unit on Concrete Slab with Optional

Outside Air Runs

Duct

Extended to

Miss Joist

To Outside Wall

Inlet Grill in Soffit

(Overhag)