COMBUSTION AIR ASSEMBLY

MODEL OAC-4 COMBUSTION AIR ASSEMBLY

1. Remove the cover plate from the 4" outlet opening location on the left outside

of the fireplace.

2. Place starting collar (4") into hole on left side of fireplace. Fireplace shortest

side of air starting collar through fireplace outer wrap. Fasten starting collar

in place with four (4) sheet metal screws provided. See Figure 13.

Note: The air starting collar extends through the fireplace outer wrap. When the air starting collar is
securely attached, it will form a seal against the fireplace wall.

3. Cut a 6" diameter opening for model OAC-4 in the outside

wall covering where the outside vent is to be located. See

Figure 15.

4. Select and cut a piece of duct long enough to attach to the

fireplace and stick out at least 3" beyond the face of the

wall to which the OAC-4 inlet air vent will be attached.

Cut duct with a standard pocket knife. See Figure 14.

DO NOT remove the
cover if the outside air
will not be connected.

W

ARNING

Figure 13 - Attaching Outside Air

Starting Collar to Left Side of Fireplace

Figure 14 - Attaching Outside Duct

to Starting Collar

OAC-4

Starting

Collar

Sheet

Metal

Screws

Left Side of

Fireplace

Shorter End of Air

Starting Collar

Air Starting

Collar

Duct

Screws

Left Side of

Fireplace

Figure 15 - Combustion Air Assembly for

Model No. OAC-4

Nail

Holes

6" Diameter

Hole

Duct

Extending

3"min.

AK-4 Inlet

Air Vent

Screw

Screws

5. If using insulating duct, push the insulation back from

one end of the duct approximately 2". See Figure 15.

6. Slip the exposed end of the duct over the starting collar

on the fireplace.

7. Using the sheet metal screws provided, secure the duct

end to the collar attached to the fireplace.

8. Nail or screw the combustion air assembly to the sur-

face of the wall.

Do not use a combustible duct. Always
use UL Listed Class 0 or 1 duct
material. If necessary to splice duct,
use Model 403 duct connector to splice
duct sections.

W

ARNING

Advertising