Troubleshooting – Monessen Hearth Natural Vent Gas Fireplace SBV400 User Manual

Page 36

Advertising
background image

36

62D4036

STANDING PILOT IGNITION

TROUBLESHOOTING

SYMPTOM

POSSIBLE CAUSE

ACTION

1. Spark ignitor

will not light

pilot after

repeated trig-

gering of piezo.

A. Wire disconnected.

B. Defective ignitor.

C. No gas or low gas pressure.

D. No Propane/LPG in tank

A. Open door and check to make sure wire is connected to ignitor.

B. Check for spark at electrode and pilot. If no spark and electrode

wire is properly connected, replace pilot assembly.

C. Check remote/manual shut off valve from fireplace. Low pres-

sure can be caused by bent lines, restricted lines, low pressure

line pressure. Consult with plumber or gas supplier.

D. Check Propane/LPG tank. Refill tank.

2. Pilot will not

stay lit after

carefully fol-

lowing lighting

instructions.

A. Defective thermocouple

B. Defective valve

A. Check that thermocouple flame impinges on thermocouple.

Clean and/or adjust pilot for maximum flame impingement.

Ensure that the thermocouple connection at the gas valve is fully

inserted and tight.

Disconnect the thermocouple from the valve, place one millivolt

lead wire on the tip of the thermocouple and the other meter lead

wire on the thermocouple copper lead. Start the pilot and hold

the valve knob in. If the millivolt reading is less than 15 mV,

replace pilot assembly.

B. If thermocouple is producing more than 15 mV, replace faulty

valve.

3. Pilot burn-

ing, valve

knob turned to

“ON”, switch

is turned to

“ON” or “RS”,

but burner will

not ignite.

A. Defective switch, wall switch,

remote control or wire

B. Pilot flame too small

C. Defective or malfunctioning ther-

mopile

D. Defective valve

A. Check switch and wire for proper connection. Place jumper

wires across terminals of switch. If burner comes on, replace

defective switch.If the switch is OK, repeat the same procedure

on remote control If burner comes on, replace remote control.

Place jumper wire across wire at gas valves (terminals marked

TH and TP/TH). If burner comes on, wires are faulty or connec-

tions are bad. Replace wire.

B. If pilot flame is not close enough to the thermopile, adjust pilot

flame.

C. Check thermopile wire connections to make sure all are tight

and that the thermopile is fully inserted into pilot assembly.

Check thermopile with a millivolt meter. Connect leads to TP

and TP/TH terminals on the control valve. If meter reading is

below 325 mV, replace pilot assembly.

D. Turn valve knob to “On” and switch to “ON.” Take a reading at

the thermopile leads (TP & TP/TH) on the valve. If the meter

reads greater than 175 mV and the burner does not light, replace

defective valve

4. Frequent pilot

outage prob-

lem.

A. Pilot flame may be too high or too

low, causing pilot safety to drop

out

A. Clean and adjust the pilot flame for maximum flame impinge-

ment on thermocouple.

5. The pilot and

main burner

extinguish

while in opera-

tion

A. Inner vent pipe leaking exhaust

gases back into system

B. Horizontal vent improperly

pitched

C. Improper vent cap installation

A. Check for flue product leak. Replace defective pipe section.

B. Check horizontal-venting piping is running upward 1/4" per

foot. Do not run the pipe level or downward.

C. Check for proper installation and freedom from debris or block-

age.

Advertising
This manual is related to the following products: