SCOM-100, User guide

21

h:

‘Hysteresis’ value in [%] of the analog input scale (0-20%) for ON/OFF
control (not relevant for PID control).

Changing the set point value

1255,id,sp

1255: Command

ID.

id:

Function block ID (1-4).

sp:

Set point value in the range of the analog input scale.

Setting the Function block state
The ON/OFF or PID control function block can be enabled or disabled with this SMS
command:

1251,id,s

1251: Command

ID.

id:

Function block ID (1-4).

s:

1: enable, 0:disable

Controlling the Function block state
A digital input can be configured to control the Enabled/Disabled status of the function
block.
The following command selects the digital input.

1252,id,m,n

1252: Command

ID.

id:

Function block ID (1-4).

m:

Module number (0 for SCOM-100 main unit, 1-8 for DI-42 I/O expansion
units)

n:

DI input number (1-4)

The following command clears the digital input function.

1253,id

1253: Command

ID.

id:

Function block ID (1-4).

Clearing the Function block configuration
The command erases the function block configuration and frees the function block
instance and the respective I/O.

1260,id

1260: Command

ID.

id:

Function block ID (1-4).


Note: Analog or digital inputs involved in ON/OFF or PID control function blocks can be

used for alarming, while involved digital outputs are dedicated to control and
cannot be remotely controlled through SMS commands.