Table 1-10. Switch problem priority listing

Priority

Failing component

Action

1

(1 of 7)

Software

a. Have customer verify that the software is configured

and operating correctly for this processor
node/system.

b. If no problem is found, continue with next highest

priority item in the list for this SRN.

c. Otherwise, power off this processor node and continue

service at “Step 0620-017” on page 1-28.

2

(2 of 7)

External clock

a. Check to see if a switch clock cable is connected at

switch adapter of this processor node.

b. If clock cable exists, reseat switch clock cable;

otherwise reseat switch data cable.

c. Run advanced diagnostics on the device “css0” and its

associated switch port.

d. If diagnostics fail with the previous SRN, check at

least one other processor node for indication of a
clock problem. If necessary, run advanced diagnostics
on this other node, using the device “css0” and its
associated switch port.

e. If more than one node has a clock problem, go to

“Step 0620-013” on page 1-28.

f. Replace the switch clock cable or switch data cable

that was just reseated in step 2 above.

g. Continue service at “Step 0620-018” on page 1-28.

3

(3 of 7)

Data cable

a. Reseat switch data cable at switch adapter of this

processor node.

b. Run advanced diagnostics on the device “css0” and

its associated switch port.

c. If diagnostics fail with the previous SRN, replace

switch data cable.

d. Continue service at “Step 0620-018” on page 1-28.

4

(4 of 7)

SPS Adapter
SP System Attachment
Adapter

a. Replace the switch adapter card on this processor

node.

b. Reconnect all cables to the processor node.
c. Continue service at “Step 0620-018” on page 1-28.

Note: Before disconnecting cables or performing service
actions on an SP-Attached Server, perform

Decoupling

and coupling code for SP-Attached Servers

in

RS/6000

SP: System Service Guide

.

5

(5 of 7)

System or I/O planar

a. Run advanced diagnostics on the “Base System” or

I/O planar. If a problem is detected, use SRN to
service.

b. Replace the system or I/O planar on this processor

node. Make sure to reinstall all parts and cables.

c. Reconnect all cables to the processor node.
d. Continue service at “Step 0620-018” on page 1-28.

6

(6 of 7)

Wrap plug or
Terminator

Check the wrap plug or terminator again to make sure
that it is not at fault.

7

(7 of 7)

All components replaced.

Call next level of support.

SP Switch function (MAP 0620)