Quantum Series Installation and Service Manual

720901120

-

12 -

No cooling (con’t)

Defective start relay located

on upper rear shelf

inside dispenser

There should be line voltage on the

black wire of the relay when

there is line voltage present on
the orange OR yellow wire.
Replace relay if it fails this test.

Compressor starts but

hums and trips overload

Seized or shorted compressor,

replace.

Compressor starts but does

not switch off of start
winding

Relay or compressor is defective.

Test and replace faulty item.

Compressor short cycles on

overload

Excessively high discharge pres-

sure due to restricted con-
denser or inoperative
condenser fan motor

Refrigerant leak

Repair leak. Evacuate and

recharge system.

No water dispensed,

concentrate only.

No water to dispenser

Restore water

Water supply line inside

refrigerated cabinet dis-
connected from pump
platform

Reconnect

Water solenoid located on

pump platform clogged
or defective

Disassemble and clean solenoid.

Replace if necessary.

Main water solenoid/

strainer located at base
of dispenser is clogged,
binding or defective

Remove and clean strainer. Con-

firm 28VDC is present at sole-
noid during dispense. Confirm
solenoid coil is not open. Disas-
semble and clean solenoid.

Water supply pressure is

greater than 80 psi (5.5
bar)

Add external regulator and lower

pressure to 50 psi (3.5 bar)