Co-linear Hearthmount Installation

The Jøtul GF 200 DV Lillehammer may be vented
through a masonry fireplace using Simpson Dura-
Vent Chimney Liner Conversion Kit 923GK. When
installed in the manner described below, this system
can improve the performance of the appliance in
cold climate situations, as well as simplify the vent
installation.
These guidelines must be followed:
1. Prior to the installation, the chimney flue must be

thoroughly cleaned and inspected by a qualified
chimney service person.

2. In a masonry chimney, a fireclay liner or listed

steel liner, must be present the entire length of
the chimney.

3. No appliance can be installed into a chimney flue

serving any other appliance of any kind.

4. The minimum length of the AIR INTAKE FLEX is 6

feet- measured off of the back of the appliance
and IT MUST EXTEND PAST THE DAMPER AREA OF
THE FIREPLACE.

5. If the intake flex does not extend the full length

of the chimney and connect to both the unit and
the termination cap, A METAL BLOCK OFF PLATE
MUST BE CONSTRUCTED AND INSTALLED ABOVE
THE UNIT PRIOR TO THE END OF THE INTAKE FLEX
AND MUST COMPLETELY SEAL THE CHIMNEY FLUE
FROM THE ROOM.

Consult with the local code authority having

jurisdiction before proceeding with this type of
installation.

Refer to the vent manufacturer’s instructions for

specific installation requirements.

WARNING: FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR

FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED

FOR USE WITH THIS APPLIANCE MAY RESULT IN

PROPERTY DAMAGE OR PERSONAL INJURY. BE SURE TO

MAINTAIN THE PROPER CLEARANCES TO

COMBUSTIBLES AS DEFINED IN THIS MANUAL AND

INM THE INSTRUCTIONS PROVIDED WITH EACH VENT
COMPONENT.

Figure 8. Co-Linear Vent System installed in a
masonry fireplace.

Figure 9. Co-Linear Adaptor dimensions with Plinth
legs.

18”

(457 mm)

21 1/2”

(546mm)

IMPORTANT NOTICE

THE USE OF AN EXISTING CHIMNEY AS

AN AIR INTAKE IS NOT COVERED UNDER

THE ANSI Z21.88-1999-CSA 2.33-M99

TEST METHODS AND RESULTING ITS/WHI

PRODUCT CERTIFICATION. THE CODE

AUTHORITY HAVING JURISDICTION

MUST BE CONSULTED PRIOR TO PRO-

CEEDING WITH THIS INSTALLATION

Intake Air

Exhaust Gases

#991
High
Wind Cap

#923GK
Top Kit

Maximum Co-
Linear Height
- 35 FT

#923GCL Co-
Linear
Appliance
Adaptor

Dual 3”
Flex Liners

Minimum Co-
Linear Height
-10 FT

Air Intake flex
pipe must
extend a
minimum of
6 ft. and
through the
damper area.

Chimney must
be sealed off
from the room
by a steel plate
at the damper
area.