Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

COOLING PERFORMANCE DATA

AIR CONDITIONER MODEL NO.

TCGD60S41S1

INDOOR COIL MODEL NO.

FC/MC/PC60

CONDENSING

ENTERING AIR

TEMPERATURE

IDCFM

1600

1800

2000

ID

DB

(°F)

80 80

75

80

80

80 80 75

80

80 80 80

75 80 80

ID

WB

(°F)

57 62 62 67 72 57 62 62 67 72 57 62 62 67 72

65

T.C.

55.8 63.8 62.1 65.2 71.9 60.3 65.7 62.8 66.7 69.8 64.8 67.5 63.5 68.2 67.8

S.C.

54.7 51.6 41.4 41.1 34.1 58.4 54.2 43.9 42.6 31.9 62.1 56.8 46.5 44.2 29.6

KW

3.0 3.0 3.0 3.1 3.1 3.0 3.0 3.0 3.1 3.1 3.0 3.1 3.0 3.1 3.1

75

T.C.

56.9 61.1 58.9 62.7 69.7 59.2 63.0 59.9 64.3 67.9 61.4 64.9 61.0 65.9 66.0

S.C.

53.9 50.4 40.5 40.0 33.5 55.8 53.1 43.1 41.8 31.5 57.7 55.7 45.6 43.6 29.5

KW

3.4 3.5 3.5 3.5 3.6 3.4 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5 3.5

85

T.C.

58.0 58.4 55.7 60.3 67.6 58.0 60.4 57.1 61.9 65.9 58.1 62.4 58.5 63.6 64.1

S.C.

53.2 49.3 39.7 39.0 32.9 53.3 52.0 42.2 41.0 31.2 53.4 54.7 44.8 42.9 29.4

KW

3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0 3.9 3.9 3.9 3.9 4.0

95

T.C.

59.1 55.7 52.5 56.9 65.5 56.9 57.8 54.3 57.0 63.9 54.7 59.8 56.0 61.2 62.2

S.C.

52.4 48.1 38.8 37.9 32.3 50.7 50.9 41.4 38.8 30.8 49.0 53.6 43.9 42.3 29.4

KW

4.3 4.3 4.3 4.4 4.5 4.3 4.3 4.3 4.4 4.4 4.3 4.3 4.3 4.4 4.4

105

T.C.

56.4 52.2 48.8 54.0 60.1 54.0 54.3 50.5 55.7 59.7 51.6 56.3 52.2 57.4 59.4

S.C.

49.7 45.9 37.5 36.5 29.7 47.9 48.3 40.0 38.7 29.4 46.2 50.6 42.5 40.9 29.0

KW

4.9 4.9 4.9 4.9 5.0 4.9 4.9 4.9 5.0 5.0 4.9 4.9 4.9 5.0 5.0

115

T.C.

53.8 48.8 45.2 50.2 54.8 51.2 50.9 46.8 51.9 55.7 48.7 53.0 48.5 53.6 56.6

S.C.

47.1 43.8 36.2 35.0 27.3 45.3 45.7 38.6 37.3 27.9 43.5 47.7 41.1 39.6 28.6

KW

5.5 5.4 5.4 5.5 5.6 5.5 5.5 5.4 5.5 5.6 5.4 5.5 5.4 5.5 5.6

125

T.C.

51.2 45.4 41.6 46.5 49.4 48.5 47.5 43.2 48.2 51.6 45.7 49.7 44.8 49.8 53.8

S.C.

44.5 41.7 34.9 33.6 24.9 42.6 43.2 37.3 35.9 26.5 40.7 44.7 39.7 38.3 28.2

KW

6.1 6.0 5.9 6.1 6.2 6.0 6.0 6.0 6.1 6.2 6.0 6.0 6.0 6.1 6.2

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Air Handlers

Coils

T.C.

S.C.

KW

FC/MC62

1.00 1.00 1.00

HC60

1.00 1.00 1.00

UC60

1.00 1.00 1.00

AHP/SHP60

1.00 1.00 1.00

AHX60

1.00

1.00

0.98

AV/SV*60

1.00 1.01 1.00

MV20D

FC/MC60D

1.00 1.01 1.00

MA20D

FC/MC60D

1.00 1.00 1.00

MV20D

FC/MC62D

1.00 1.01 1.00

MA20D

FC/MC62D

1.00 1.00 1.00

F5FP060

1.00 1.00 1.00

F6FP060

1.00

1.00

0.96

F4FV060 –

1.00

1.00

0.99

Furnaces

Coils

T.C.

S.C.

KW

T*(8,L)X*C16

FC/PC60C

0.99

0.98

0.99

T*(8,L)X*C20

FC/MC/PC60D

1.00

0.98

1.00

T*9X*C16

FC/PC60C

0.98

0.98

0.98

T*9X*C20

FC/PC60C

0.98

0.98

0.98

T*9X*D20

FC/MC/PC60D

0.99

0.98

0.99

T*9X*C20

FC/MC/PC60D

0.99

0.98

0.99

T*(8,L)X*C20

FC/MC62D

1.00

0.98

1.00

T*(8,L)X*C16

UC60C

0.98

0.97

0.98

T*(8,L)X*C20

UC60D

0.99

1.00

0.99

T*9X*C16

FC/PC60C

0.98

0.97

0.98

T*9X*C20

FC/PC60C

0.98

0.97

0.98

T*9X*D20

UC60D

0.98

0.97

0.98

T*(8,L)X*C20

UC60D

0.99

1.00

0.99

T*9X*C20

UC60D

0.98

0.97

0.98

(T*9C/T*9V)*D20 FC/MC/PC60D

0.97 0.95 0.96

T*(8,L)C*C20

FC/MC62D

0.99 0.97 0.94

(T*9C/T*9V)*C20 FC/MC62D

0.98 0.96 0.97

(T*9C/T*9V)*D20 FC/MC62D

0.99 0.96 0.96

T*(8,L)C*C20

FC/PC60C

0.98 0.96 0.94

(T*9C/T*9V)*C20 FC/PC60C

0.97 0.95 0.96

(T*9C/T*9V)*D20 HC60

0.94 0.93 0.95

T*(8,L)C*C20

UC60C

0.95 0.91 0.93

(T*9C/T*9V)*C20 UC60C

0.94 0.90 0.96

(T*9C/T*9V)*D20 UC60D

0.94 0.90 0.95

Advertising