Slant/Fin GXHA Series User Manual

Ratings chart – gas boilers, Galaxy gx (h), gxha series

Advertising
background image

®

RATINGS CHART – GAS BOILERS

GALAXY GX (H), GXHA SERIES

©Slant/Fin Corp. 2007

GXHA-100

100,000

81,000

61,000

254

2

1/

2

GXH-105

105,000

86,000

495

75,000

2

1/

2

GXHA-120

120,000

97,000

73,000

304

3

GXH-125

126,000

104,000

600

90,000

3

GXH-150

147,000

120,000

695

104,000

3

1/

4

GXHA-160

160,000

130,000

98,000

408

3

1/

2

GXH-170

168,000

137,000

795

119,000

3

1/

2

GXH-190

189,000

155,000

895

135,000

3

3/

4

GXHA-200

200,000

163,000

122,000

508

4

GXH-210

210,000

172,000

995

150,000

4

GX-225

225,000

184,000

1065

160,000

4

GXH-230

231,000

189,000

189,000

1095

164,000

142,000

591

4

1/

4

GX-250

250,000

204,000

1180

177,400

4

1/

2

GXH-250

252,000

206,000

206,000

1195

179,000

155,000

646

4

1/

2

GXH-275

273,000

223,000

223,000

1290

194,000

167,000

696

5

GXH-300

300,000

240,000**

240,000 **

1395

209,000

180,000

750

5

1/

2

GXH-300H§

300,000

243,000**

243,000 **

1405

211,000

182,000

758

5

1/

2

MODEL

NUMBER †

CSA

INPUT
(Btuh)

D.O.E.

CAPACITY

WATER

(Btuh)

D.O.E.

CAPACITY

STEAM

(Btuh)

WATER

(Sq.Ft.)

WATER

(Btuh)

STEAM

(Btuh)

STEAM
(Sq.Ft.)

TANKLESS

HEATER

CAPACITY

(G.P.M.)‡

RATINGS STEAM OR WATER

NET I=B=R*

EFFICIENCY

GALAXY DOE SEASONAL

EFFICIENCY (AFUE)*

GXH-105 ED

81.00

GXH-125 ED

81.00

GXH-150 ED

81.14

GXH-170 ED

81.14

GXH-190 ED

81.14

GXH-210 ED

81.17

GX-225 ED

81.30

GXH-230 ED

81.21

GX-250 ED

80.70

GXH-250 ED

81.24

GXH-275 ED

81.28

GXHA-100 ED

81.00

GXHA-120 ED

81.20

GXHA-160 ED

81.20

GXHA-200 ED

81.30

MODEL

Natural and L.P. Propane Gas

± GG models: Add suffix “S” for standard water boiler, “P” for

packaged water boiler. Add suffix “E” for intermittent pilot igni-
tion system (available only with 24 volt gas valve). Type of
gas: After model number, specify gas by name “Natural” or
“Propane”

*

Net ratings are based on a piping and pick-up allowance of
1.33 (steam) and 1.15 (hot water). Slant/Fin should be con-
sulted before selecting a boiler for installation having
unusual piping and pick-up requirements. Ratings must

be reduced by 4% at 2,000 feet elevation and an addition
al 4% for every additional 1,000 feet elevation over 2,000
feet.

† GXH and GX models: Add suffix “PT” for standard water

boiler with tankless heater, “PZ” for steam boiler, “PZT” for
packaged steam boiler with tankless heater. Add suffix “E”
for intermittent pilot ignition system (available only with 24
volt gas valve). Type of gas: After model number, specify
gas by name “Natural” or “Propane”.

** CSA output rating (Btuh).
§ Ratings for GXH-300H are for natural gas only.
‡ Tankless heater ratings based on intermittent draw.
NOTE: All boilers under 300,000 Btu input are tested and
rated for capacity under the U.S. Dept. of Energy (D.O.E.)
Test Procedure for boilers.

* Includes intermittent pilot and

vent damper. Annual Fuel
Utilization Efficiency based on
constant circulation for hot
water models.

SLANT/FIN CORPORATION, Greenvale, NY 11548 • Phone: (516) 484-2600

FAX: (516) 484-5921 • In Canada: Slant/Fin LTD/LTEE, Mississauga, Ontario

www.slantfin.com

DISCONTINUED MODEL

NOTE: GXH-230 (WATER MODEL DISCONTINUED ONLY)

STEAM MODELS ARE AVAILABLE

Advertising