Modular Boiler Submittal Data

A Caravan modular boiler system consists of
two or more compact cast-iron boilers that offer
significant advantages in terms of installed
cost, efficiency and reliability. Caravan
systems are based on step-firing just enough
modules to meet hot water or space heating
demands. LDWO systems are available in
602,000 to multi-million Btuh gross input.
For additional information, see Caravan
Engineering Manual, pub. C-30 and Caravan
oil application guide, pub. CG-10-HWO.

Standard Equipment

One per module unless otherwise noted
Pre-assembled cast-iron heat exchanger
with built-in air separators and insulated jacket
Swing-out/removable burner door
Flame retention oil burner, with nozzle;

cadmium sulfide flame detector

Hi-limit control, auto reset
Primary burner control
System pressure and temperature gauge

(unmounted)

Module pressure and temperature gauge
Module pressure relief valve (ASME)

(unmounted) Specify 30, 50 or 100 psi.

Draft regulator (unmounted)

Optional Equipment
Hot water supply and return header

assemblies

Control panel with automatic lead lag

Control header (unmounted,

one per system)

Flue brush
Module drain cock

(unmounted)

LDWO SERIES—Oil-fired/Hot Water

Ratings

Oil Caravan ratings/hot water models — LDWO Series

LDWO-600-2-5

2

4.30

602

500

2900

435

14.9

31.0

1570

2"

LDWO-750-2-6

2

5.20

728

596

3453

518

17.8

35.6

1790

2"

LDWO-850-2-7

2

6.00

840

684

3967

595

20.4

45.2

2000

3"

LDWO-900-3-5

3

6.40

896

750

4347

652

22.4

46.5

2355

3"

LDWO-1100-3-6

3

7.80

1092

894

5180

777

26.7

53.4

2685

3"

LDWO-1300-3-7

3

9.00

1260

1026

5947

892

30.6

67.8

3000

3"

LDWO-1700-4-7

4

12.00

1680

1368

7933

1190

40.9

90.4

4000

3"

LDWO-2100-5-7

5

15.00

2100

1710

9913

1487

51.1

113.0

5000

3"

LDWO-2500-6-7

6

18.00

2520

2052

11893

1784

61.3

135.6

6000

3"

LDWO-2900-7-7

7

21.00

2940

2394

13880

2082

71.5

158.2

7000

4"

LDWO-3400-8-7

8

24.00

3360

2736

15860

2379

81.7

180.8

8000

4"

Model No.

No. of

Modules

I=B=R

Firing

Rate

#2 Oil

GPH*

Input

EDR

Water †

(Sq. Ft.)

I=B=R

Net

Output‡

(MBH)

Boiler

Horse-

power

Water

Content

(gal.)

Recom-

mended

Header

Size §

Ship

Wt.

Gross

Output

I=B=R Ratings

(MBH)

* Light oil, 140,000 Btuh per gallon.
† Based on 150 Btuh per square foot E.D.R. at 170°F average

water temperature.

‡ Net ratings are based on a piping and pick-up allowance of

1.15. Slant/Fin should be consulted before selecting a boiler

for installation having unusual piping and pick-up requirements.

§ Modules in excess of 8 are piped in parallel to first eight.

NOTE: For higher capacities, specify any combination of standard

Caravan models shown.

®