Modular Boiler Submittal Data

A Caravan modular boiler system consists of
two or more compact cast-iron boilers that offer
significant advantages in terms of installed
cost, efficiency and reliability. Caravan
systems are based on step-firing just enough
modules to meet space heating demands.
LDZO systems are available in 602,000 to
multi-million Btuh gross input. For additional
information, see Caravan Engineering
Manual, pub. C-30.

Standard Equipment

One per module unless otherwise noted
Pre-assembled cast-iron heat exchanger

with insulated jacket

Flame retention oil burner, with nozzle;

cadmium sulfide flame detector

Primary burner control
System pressure gauge and siphon

(unmounted, one per system)

Module pressure gauge and siphon

(unmounted)

Module pressure relief valve (ASME)

(unmounted) 15 PSI.

Draft regulator (unmounted)
Flue brush

ASME Required Options
67 Low water cut off (one per module)
PA404A Pressure control (one per module)
67M Low water cut off (one per system)
L4079B Manual reset pressure control

(one per system)

Module drain cock

(unmounted)

Water level sight glass

(unmounted)

LDZO SERIES—Oil-Fired/Steam

Ratings

Oil Caravan ratings and dimensions/steam models — LDZO Series

LDZO-600-2-5

2

4.3

602

500

85.90

375

1563

14.9

21.4

1426

3"

LDZO-750-2-6

2

5.2

728

596

85.80

447

1863

17.8

25.2

1630

3"

LDZO-850-2-7

2

6.0

840

684

85.50

513

2138

20.4

29.0

1838

3"

LDZO-900-3-5

3

6.4

896

750

85.90

563

2345

22.4

32.1

2139

3"

LDZO-1100-3-6

3

7.8

1092

894

85.80

671

2796

26.7

37.8

2445

5"

LDZO-1300-3-7

3

9.0

1260

1026

85.50

770

3208

30.6

43.5

2756

5"

LDZO-1700-4-7

4

12.0

1680

1368

85.50

1035

4313

40.9

58.0

3675

6"

LDZO-2100-5-7

5

15.0

2100

1710

85.50

1319

5496

51.1

72.5

4594

6"

Model No.

No. of

Heating

Modules

Burner

Capacity

(GPH)*

Input

(MBH)

Net

Output

MBH†

Comb.

Efficiency

Sq.Ft

Steam‡

Horse-

power

Boiler

Water

Content

(gal)

Recom-

mended

Header

Size

Weight

with

Water

Gross

Output

MBH

* Light oil, 140,000 Btu. per gallon.
† Net ratings are based on piping and pick-up allowance of 1.33.

Slant/Fin should be consulted before selecting a boiler for
installation having unusual piping and/or pick-up requirements.
For higher elevations, input may need to be reduced

‡ Based on 240 Btuh per square foot E.D.R. at 215˚F average

steam temperature.

Modules in excess of 5 are piped in parallel in two or more
banks.

®

I=B=R

Ratings for No. 2 Oil

Advertising