3 rules for configuring a network – Siemens Automation System S7-400 User Manual

Page 105

Advertising
background image

Networking

5-7

Automation System S7-400 Hardware and Installation

A5E00850741-01

5.3

Rules for Configuring a Network

Rules

Observe the following rules for connecting the nodes of a network:

• Before you interconnect the individual nodes of the network, you must assign to

each node the MPI address and the highest MPI address or PROFIBUS-DP

address.
Tip: Mark the address of each node in a network on the housing. To do this, use

the adhesive labels enclosed with the CPU. You can then always see which

address is assigned to which node in your plant.

• Before you insert a new node in the network, you must switch off its supply

voltage.

• Connect all the nodes in the network in a row. In other words, include the fixed

programming devices and operator panels directly in the network.
Only use spur lines for connecting the programming devices / OPs to the

network which are needed for startup or maintenance.

• If you operate more than 32 nodes in a PROFIBUS-DP network, you must

connect the bus segments via RS 485 repeaters.
In a PROFIBUS-DP network, all bus segments together must have at least one

DP master and one DP slave.

• You connect ungrounded bus segments and grounded bus segments via

RS 485 repeaters (see Reference Manual CPU Data, Chapter 10).

• The maximum number of nodes per bus segment decreases with each

RS 485 repeater. This means that if there is an RS 485 repeater in a bus

segment, there may only be a maximum of 31 other nodes in a bus segment.

However, the number of RS 485 repeaters has no effect on the maximum

number of nodes on the bus.
Up to ten segments can be connected in series.

• Switch on the terminating resistor at the first and last node of a segment.

To ensure the bus operates without interference, you should not switch off these

nodes.