Maintenance

7-9

Automation System S7-400 Hardware and Installation

A5E00850741-01

7.5

Changing the Fuses in the Digital Modules

Modules with Fuses

The following modules have fuses which you can change yourself if they are
defective:

• Digital output module SM 422; DO 16 x DC 20--125 V/1,5A

(6ES7422-5EH10-0AB0)

• Digital output module SM 422; DO 16 x AC 20-120 V/2A

(6ES7422-5EH00-0AB0)

• Digital output module SM 422;DO 8 x AC 120/230 V/5A

(6ES7422-1FF00-0AA0)

• Digital output module SM 422;DO 16 x AC 120/230 V/2A

(6ES7422-1FH00-0AA0)

Check the Plant

Correct the faults which led to the fuses blowing.

Changing the Fuses

To change the fuses in a digital module, you must remove the front connector from
the digital module and remove the module from the rack.

!

Warning
Improper handling of the digital modules can result in injury and damage.
Hazardous voltages of >25 VAC or >60 VDC may be present below the covers on

the right-hand side of the module.
Before you open these covers, ensure that either the front connector for the

module is removed or the module is disconnected from the voltage supply.