1 fiber-optic cables – Siemens Automation System S7-400 User Manual

Page 122

Advertising
background image

Networking

5-24

Automation System S7-400 Hardware and Installation

A5E00850741-01

PROFIBUS Optical Bus Terminal (OBT)

A PROFIBUS node can be connected to the optical PROFIBUS-DP network via a

PROFIBUS Optical Bus Terminal (OBT) (6GK1 500-3AA00) without an integrated

fiber-optic cable interface (e.g. programming devices (PGs) or operator panels

(OPs), see Figure 5-13).
The programming device/PC is connected to the RS 485 interface of the OBT by

means of the PROFIBUS cable. The OBT is integrated in the optical

PROFIBUS-DP line by means of its fiber-optic cable interface.

5.8.1

Fiber-Optic Cables

Features of the Fiber-Optic Cables

Use Siemens plastic and PCF fiber-optic cables with the following features:

Table 5-4

Features of the Fiber-Optic Cables

Description

SIMATIC NET PROFIBUS

Plastic Fiber-Optic

Duplex Conductor

Plastic Fiber-Optic

Standard Cable

PCF Fiber-Optic

Standard Cable

Standard designation

I-VY2P 980/1000

150A

I-VY4Y2P 980/1000

60A

I-VY2K 200/230

10A17+8B20

Field of application

Indoors with a low

mechanical load,

such as laboratory

test assemblies or in

cabinets:
Cable lengths up to

50 m

Indoor applications:
Cable lengths up to

50 m

Indoor applications:
Cable lengths up to

300 m

Fiber type

Step-index fiber

Core diameter

980 μm

200 μm

Core material

Polymethyl methacrylate (PMMA)

Quartz glass

Cladding outer diameter

1000 μm

230 μm

Cladding material

Fluorinated special polymer

Inner sheath

•

Material

•

Color

•

Diameter

PVC

Gray

2.2  0.01 mm

PA

Black and orange

2.2 ± 0.01 mm

--

(Without inner sheath)

Outer sheath

•

Material

•

Color

--

PVC

Purple

PVC

Purple

Number of fibers

2

Attenuation at
wavelength

≤ 230 dB/km

660 nm

≤ 10 dB/km

660 nm

Advertising