Siemens Automation System S7-400 User Manual

Page 74

Advertising
background image

Wiring the S7-400

4-14

Automation System S7-400 Hardware and Installation

A5E00850741-01

Connecting the Load Voltage Ground

Many output modules require an additional load voltage to switch the actuators.
Two different modes are possible for this load voltage:

• Non-isolated operation

• Floating operation
The following table shows how the load voltage ground is connected in the
individual modes.

Table 4-3

Grounded connection load voltage

Mode

Connection of Load Voltage

Non-isolated operation

•

Grounded configuration

•

Ungrounded configuration

to the reference point of the rack; metallic connection

between frame element and chassis ground must be

fitted.

to the reference point of the rack; metallic connection

between frame element and chassis ground must be

fitted.

Floating operation

•

Grounded and ungrounded

configuration

Left open or to any point, but not to protective ground

or reference potential M of operating voltages

The following figure shows how the load voltage ground is connected for
non-isolated operation.

Metallic connection, remove for

ungrounded configuration

Ground terminal for

load voltage

Figure 4-7 Grounded connection load voltage