CONFIGURING THE HOST COMPUTER PORT

UNILINK HOST ADAPTER

3–11

USER MANUAL

BDLC Host Command

BDLC Host Command

RR, “Poll”

RR, “Poll”

RR, “Message Received”

RR, “Message Received”

First Network Response

Second Network Response

Host

Computer

UNILINK

Host

Adapter

Figure 3–9

BDLC Multiple Outstanding Transactions

Another consideration is that of the six configurable modes described in
Chapter 2, two of those modes emulate the original TIWAY I Host Adapter,
meaning that they require the NITP protocol. If you plan to use either the
Master Host Interface Unit (MHIU) or Host Interface Unit (HIU) in EHA mode,
you must also use the NITP protocol because these modes do not support
commands for configuring network parameters and the dipswitch used to
define the BDLC address is used to define those network parameters.

Another factor to consider is the type of secondary devices that will be on your
network. If you will be connecting Computer Interface Modules (CIM) or
Intelligent Tank Transmitters (ITT) in CIM mode, you must configure the
adapter as an MHIU/EHA which requires the NITP protocol. ITTs may also be
used in the TIWAY mode without the above restriction.