Timer remote controller (rcs-tm80bg) – Sanyo AHX0752 User Manual

Page 52

Advertising
background image

2-32

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Remote Control Functions

3. Timer Remote Controller (RCS-TM80BG)

0000

Not displayed

0001

150 hours

0002

2,500 hours

0003

5,000 hours

0004

10,000 hours

Filter sign ON time

(filter lifetime)

0005

Use the filter clogging sensor.

0000

Standard (setting at time of shipping)

Degree of filter fouling

0001

Highly fouled
(Filter sign ON time is reduced to one-half the set time.)

0001

Central control address 1

0002

Central control address 2

0003

Central control address 3

0064

Central control address 64

Central control address

0099

No central control address set (setting at time of shipping)

0000

Normal (setting at time of shipping)

Operating mode

priority change

0001

Priority

Compressor ON

Compressor OFF

0000

MED 1 min., LO 3 min.

LO

0001

MED

LO

0002

LO

LO

0004

MED 1 min., LO 3 min.

MED

0005

MED

MED

Fan speed when

heating thermostat is

OFF

0006

LO

MED

0000

No shift

0001

0002

0003

0004

0005

Heating intake

temperature shift

0006

0000

No heater

Electric heater

installation

0001

Heater installed

0000

No (setting at time of shipping)

Hu

Change to remote

controller sensor

thermostat differential

Mode

dependency

midifying when

heater thermostat is

OFF

0001

Yes

0000

Thermostat OFF differential: – 2°F (– 1°C) (setting at time of shipping)

Thermostat OFF differential: – 1°F (– 0.5°C)

0001

0000

Normal

0001

0000

Normal

Cooling-only

0001

Cooling only

List of Simple Setting Items

Shifts intake temperature 2°F (1°C) down.

Shifts intake temperature 4°F (2°C) down.

Shifts intake temperature 6°F (3°C) down.

Shifts intake temperature 8°F (4°C) down.

Shifts intake temperature 10°F (5°C) down.

Shifts intake temperature 12°F (6°C) down.