Remote Control Functions

Setting data

Item

code

Item

No. Description

0000 No forced operation

0001 Forced operation for 1 minute

Automatic drain pump

operation

0060 Continuous

operation

0000 None

Ventilation fan operation

0001 Ventilation fan operated by remote controller.

0000 Not used. (Body sensor is used.)

Wired remote controller sensor

0001 Remote control sensor is used.

0000 Normal

(displayed)

“ Operation change control in

progress ” display

0001 Not

displayed

0000 None

OFF reminder function for

when weekly timer is used

RAP valve

Discharge temperature control

0001 Only stop time setting is enabled.

0013

0000 Discharge temperature control OFF
0001 Discharge

temperature

control

ON

0000 RAP valve control OFF
0001 RAP valve control ON

0014

0025

Heat exchanger temperature

for cold air discharge

(Heat exchanger control point

for control to prevent cold air)

0026

0000

Output linked with fan. (ON when indoor unit fan is
operating.)

Fan

output

switching

0001 Fan

mode

operation

output

0000 No

delayed

start

0001 1 sec. delayed start

0002 2 sec. delayed start

0058 58

sec. delayed start

0059 59

sec. delayed start

Drain pump delayed start time

0060 60

sec. delayed start

0000 Humidifier output OFF. Drain pump stopped.

0001 Humidifier output ON. Drain pump operates.

0002

Humidifier output ON. Drain pump operates for 1 minute
when total humidifier operating time reaches 60 minutes.

Humidifier

setting

0003 Humidifier output ON. Drain pump stopped.

0000 Standard

setting

Flap operation mode

0001

Draft reduction mode (Flap lower-limit position is shifted

upwards.)

0000

Smudging reduction mode (Flap swing upper-limit position
is shifted downwards.)

0001 Normal

mode

Flap swing mode

0002

Draft reduction mode (Flap swing lower-limit position is

shifted upwards.)

Control temperature 55

°

F (13

°

C )

Control temperature 57

°

F (14

°

C )

Control temperature 77

°

F (25

°

C )

Control temperature 78

°

F (26

°

C )