W-2way eco-i alarm codes – Sanyo AHX0752 User Manual

Page 70

Advertising
background image

3-8

Trouble Diagnosis

1

2

3

4

5

6

7

8

3. W-2WAY ECO-i Alarm Codes

E25 Alarm

Alarm code

E25


Alarm meaning

Outdoor unit address setting failure (duplication)

Alarm conditions

Communication by the outdoor unit main/sub control wiring was received that contained the
same address as that unit 5 times or more within 3 minutes.

Probable cause

The unit number is set incorrectly.

Check

Check the unit number again.

Correction

Correct the incorrect unit number setting.

Example

Notes

Recovery from this alarm occurs automatically (when communication that contains the same
address is not received for 3 minutes).

E26 Alarm

Alarm code

E26

Alarm meaning

Mismatch in outdoor unit quantity

Alarm conditions

After power initialization, the set outdoor unit quantity did not match the number of outdoor units
detected on the outdoor unit main/sub control wiring for 3 minutes or longer.

Probable cause

(1) The outdoor unit quantity is set incorrectly.
(2) The outdoor unit main/sub control wiring is cut.

Check

(1) Check the outdoor unit quantity setting again.
(2) Check the outdoor unit main/sub control wiring.

Correction

(1) Correct the incorrect outdoor unit quantity setting.
(2) Repair the outdoor unit main/sub control wiring.

Example
Notes

Recovery from this alarm occurs automatically (when the set outdoor unit quantity matches the
number of outdoor units detected on the outdoor unit main/sub control wiring).

E29 Alarm

Alarm code

E29

Alarm meaning

Outdoor unit (sub) failed to receive signal from outdoor unit (main).

Alarm conditions

Outdoor unit (sub) communications from outdoor unit (main) were interrupted for 3 minutes or longer.

Probable cause

(1) After initial communications were completed, the outdoor unit main-sub control wiring was

cut.

(2) After initial communications were completed, the RC connector (CN006) became disconnected.
(3) The power at the outdoor unit (main) is turned OFF.

Check

(1) Check the outdoor unit main/sub control wiring.
(2) Check the RC connectors.
(3) Check the power at the outdoor unit (main/sub).

Correction

(1) Repair the outdoor unit main/sub control wiring.
(2) Correct the RC connector connection.
(3) Turn ON the outdoor unit (main/sub) power.

Example
Notes

Advertising