6 Configuring and Programming the CP as a PROFINET IO Device

B3L−25

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007
C79000-G8976-C198-04

Result:

You will see the connector symbol for the PROFINET IO system beside the

PROFINET IO controller.

Step 2: Configuring the PROFINET IO device on the PROFINET IO controller

1. Open the hardware catalog and select a version of the CP V2.0 or higher as the

PROFINET IO device from the folder “PROFINET IO”

"

“I/O”

"

“SIMATIC S7−CP”

"

“CP 343−1 Lean”.

2. Connect the CP with the PROFINET IO system (drag and drop).
3. Add input and output modules with the required I/O data length (1 to max. 240

bytes) to the PROFINET IO device.

The following screenshot shows the configuration table of the PROFINET IO
controller with an S7−400 station as PROFINET IO controller. The PROFINET IO
device shown here, for example, has three modules for process inputs (I address)
and process outputs (O address).

Figure 6-4

SIMATIC Station with PROFINET IO System with the CP as Device with Input (DI) and

Output Modules (DO)