9 Further Notes on Operation

B3L−51

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007
C79000-G8976-C198-04

S The connections on which a job on the communication bus with a data length >

240 bytes is being processed are aborted temporarily.

S FETCH/WRITE connections are temporarily aborted.
On the FC interface in the user program, the condition codes made up of the
DONE, ERROR and STATUS parameters must be evaluated in FC11 / FC12.

9.6

Special Features of IP Configuration

Configured S7 connections cannot be operated if the IP address is assigned

over DHCP

Notice
If you obtain the IP address over DHCP, any S7 connections you may have
configured will not work. Reason: The configured IP address is replaced by the
address obtained over DHCP during operation.

9.7

Reserved Port Numbers

The following local port numbers are reserved; You should not use these for other
purposes in the connection configuration.

Table 9-1

Reserved Port Numbers

Protocol

Port number

Service

TCP

20, 21

FTP

TCP

25

SMTP

TCP

80

HTTP

TCP

102

RFC1006

TCP

135

RPC−DCOM

UDP

161

SNMP_REQUEST

UDP

34964

PN IO

UDP

65532

NTP

UDP

65533

NTP

UDP

65534

NTP

UDP

65535

NTP