9 Further Notes on Operation

B3L−47

CP 343-1 Lean for Industrial Ethernet / Manual Part B3L

Release 03/2007
C79000-G8976-C198-04

Behavior after Memory Reset

The CPU in the S7 station does not recognize that the CP memory was reset. The
CP therefore changes to the “stopped with error” state (see Chapter 4).

The configuration data must then be reloaded.

You can initiate this loading by turning the power off and on again.

9.2

Working with Fast Ethernet − automatic switchover

How Automatic Switchover of the Network Settings Works

The CP has two 10/100 Mbps half/full duplex ports with autosensing and
autonegotiation of the network settings. After turning on the CP, these functions
work as explained below:

S The CP attempts to detect the transmission rate (10/100 Mbps) being used by

the partner.
If no connection is established between partners in PROFINET IO mode, you

should check whether the devices involved are set to “automatic setting” or

100 Mbps full duplex.

S If detection is possible, the CP attempts to negotiate a full duplex with the

partner.

S If no negotiation is possible, the CP uses the previously detected transmission

rate and half duplex.

Duration of the procedure: up to 2 seconds

You set the network properties of the CP in STEP 7 in the properties dialog of the
CP, “Port Parameters” tab.

Autocrossing

The automatic setting also includes an “autocrossing” mechanism. With
autocrossing, you can connect network components and end devices using either
crossover or straight−through cables.