Check list, Table 1 demand signals − humiditrol, Eda enabled – Lennox International Inc. 505 User Manual

Page 12

Advertising
background image

Page 12

EDA 01/06

Check List

n Checkpoint

What to Check

Action

Thermostat and
Sensor

Wiring

Confirm Sensor connected to SignatureStat

t using twisted pair

wire (see wiring diagram figure 13)

Thermostat

Humiditrol

®

Installer Settings

Confirm HUMIDITROL is enabled (see figure 8)

Thermostat

Humiditrol

®

User Settings

Confirm HUMIDITROL − Dehumidify − ON is selected (see figure 8)

Thermostat

Humiditrol

®

User Settings

Confirm Relative Humidity setting (see figure 8)

Indoor Unit

Variable-Speed Blower Settings

Confirm Settings for D": CFM = 60% to 65% of 2nd-stage cool
(see indoor unit installation instructions and table 1, below)

Insulation

Charge Compensator

C

fi

i

l ti

i

l i

t ll d (

h

t

kit

Insulation

Liquid Line

Confirm insulation is properly installed (see charge compensator kit
instructions; also, see figure 5)

Insulation

Vent Line to Suction Line

instructions; also, see figure 5)

Charge Compen-
sator

1/4"Line

Confirm 1/4" port oriented downward (see charge compensator
details, figure 5)

Check/Flow Re-
strictor

3/8" Line

Confirm restrictor installed/oriented properly (see check/flow restric-
tor details figure 5)

System Charge

Refrigerant

With unit running in cooling mode, check and confirm system is
properly charged (see outdoor unit installation instructions).

Outdoor Unit

Fan Relay

Confirm (if unit has variable speed outdoor fan) relay is installed
properly (see wiring diagram figures 12 and 13)

Outdoor Unit

EDA Label

Confirm label is installed in prominent location and will be easily
visible during servicing.

NOTE − System will NOT operate in dehumidification mode with outdoor temperature at or above 95ºF.

Operational Status

Dehumidification Mode

Record supply air temperature and confirm temperature that it is
higher than in cooling mode.

Operational Status

Dehumidification Mode

On units with variable speed outdoor fan, check that fan operates
at approximately 250 rpm (lowest speed).

Table 1

Demand Signals − Humiditrol

®

EDA Enabled

Operating Sequence

System Demand

System Response

Thermostat Demand

Relative Humidity

Com

Blower

CFM

System Type

Step

Y1

Y2

O

G

Status

D

Com-

pressor

CFM

(Cool) %

Comments

Cooling Operation − No call for dehumidification

Single-stage outdoor unit

1

ON

(na)

ON

ON

Acceptable

24 VAC

High

100

Compressor and indoor

bl

f ll

th

t t

Two-stage outdoor unit Y1

1

ON

ON

ON

Acceptable

24 VAC

Low

70

p

blower follow thermostat

demand

Two-stage outdoor unit Y2

2

ON

ON

ON

ON

Acceptable

24 VAC

High

100

demand

Demand for Dehumidification and Cooling

Single-stage outdoor unit

1

ON

(na)

ON

ON

Demand

24 VAC

High

100

Cooling operation has

i it

Two-stage outdoor unit Y1

1

ON

ON

ON

Demand

24 VAC

Low

70

g p

priority

Two-stage outdoor unit Y2

2

ON

ON

ON

ON

Demand

24 VAC

High

100

Dehumidification Mode Only − No Cooling Demand

Single-stage outdoor unit

1

ON

(na)

ON

ON

Demand

0 VAC

High

50 − 70*

A Humiditrol

®

EDA−

equipped system is allowed
to operate and cool room
temperature below set point
(but only by 2ºF) when try-

Two-stage outdoor unit Y2

2

ON

ON

ON

ON

Demand

0 VAC

High

50 − 70*

(but only by 2 F) when try
ing to satisfy a persisting
humidity set point; it is not
allowed to operate at all
when outdoor temperature
is >95ºF.

* NOTE − Blower CFM speed (percentage) will vary depending on selected indoor equipment (furnace, coil blower, etc.).