Eda installation & checkout flow chart figure 4 – Lennox International Inc. 505 User Manual

Page 6

Advertising
background image

Page 6

EDA 01/06

Required Parts (all applications)

EDA Unit, with check/flow restrictor & label

Appropriate SignatureStat

t Thermostat

46M98 − Outdoor Sensor

84X49 − Twisted Pair Wire
Appropriate Insulation and Piping Kit

Required Parts (2−Stage Heat Pump appl.)

12P61 − 75VA Transformer (for HP applications)

Installation Process

YES

NO

NO

YES

ENSURE ALL POWER IS OFF

INSTALL EDA UNIT IN DUCT

SYSTEM

INSTALL THE CHARGE

COMPENSATOR (IF REQUIRED)

IN CONVENIENT LOCATION

(SEE FIGURE 5)

MAKE ALL REFRIGERATION

CONNECTIONS, BEING SURE

TO INSTALL THE CHECK/FLOW

RESTRICTOR (SEE FIGURE 5)

LEAK CHECK THE SYSTEM

WITH 3−WAY VALVE ASSEMBLY

SET TO EVACUATE" (SEE

FIGURE 7)

INSULATE ALL REFRIGERANT

LINES

EVACUATE THE SYSTEM AS

DESCRIBED IN THE OUTDOOR

UNIT INSTALLATION

INSTRUCTIONS

INSTALL OUTDOOR SENSOR

PROCURE

MISSING PARTS

ARE

ALL REQUIRED

PARTS

AVAILABLE

?

IS

THE

OUTDOOR

TEMPERATURE

BELOW

95ºF

?

SET COOLING SETPOINT ON ROOM THERMOSTAT
TO 2 DEGREES ABOVE INDOOR TEMPERATURE
(OUTDOOR UNIT WILL TURN OFF)

NOTE − A Humiditrol

®

EDA−equipped system is allowed

to operate and cool room temperature below set point
(but only by 2ºF) when trying to satisfy a persisting hu-
midity set point.

DEHUMIDIFICATION

IS DE−ACTIVATED;

CHECK FOR

CORRECT

OPERATION AT A

TIME WHEN

AMBIENT

TEMPERATURE IS

BELOW 95ºF.

OUTDOOR UNIT:
COMPRESSOR IN HIGH STAGE;
FAN IN LOWEST SPEED;

EDA:
3−WAY VALVE ASSEMBLY TO DEHUMIDIFICATION"
POSITION
INDOOR UNIT:
FAN IN DEHUMIDIFICATION SPEED

CHECK THE TEMPERATURE DIFFERENCE
ACROSS THE EDA COIL AND THE LIQUID LINE
TEMPERATURES AS NOTED IN FIGURE 9 ON
PAGE 10

Check Dehumidification Operation

MAKE WIRING CONNECTIONS

AS SHOWN IN FIGURES 12 & 13

(SEE PAGES 14 AND 15)

INSTALL EDA" LABEL ON

OUTDOOR UNIT

POWER UP THE INDOOR UNIT

CHECK THAT 3−WAY VALVE

ASSEMBLY IS SET TO

COOLING" POSITION AS

SHOWN IN FIGURE 7

ENABLE HUMIDITROL ON

ROOM THERMOSTAT (SEE

FIGURE 8)

SET THERMOSTAT FOR

MAXIMUM COOLING

OPEN REFRIGERANT VALVES

TURN OUTDOOR UNIT MAIN

POWER ON

CHECK CHARGE AND CHARGE

AS NEEDED (SEE PAGE 8)

start

EDA Installation & Checkout Flow Chart

Figure 4

SET DEHUMIDIFICATION SETPOINT TO 5% BELOW
CURRENT ROOM RELATIVE HUMIDITY

Advertising