EDA INSTALLATION/ SERVICE INSTRUCTIONS

Insulating and Sealing the Unit

IMPORTANT

All piping, metering devices, and connections must
be insulated to prevent moisture damage caused by
sweating.

Seal the unit so that warm air is not allowed into the cabi-
net. This is especially important when the unit is installed in
an unconditioned area. Make sure the liquid line entry
points are sealed with either refrigerant tube insulating ma-
terial or with Permagum (see figure 5 on page 7).

Other System Components

Blower Control

EDA units are to be applied with an indoor unit that has a
variable speed motor (VSM). Refer to the indoor unit instal-
lation instruction for setting blower speed.

Thermostat and Sensor

IMPORTANT

A SignatureStat

t thermostat and properly-

connected outdoor sensor is REQUIRED for the
EDA unit to function properly. Twisted pair wire
(84X49 or equivalent) is REQUIRED between the
SignatureStat and the outdoor sensor.

Install the remote sensor on the outside of a northern wall
of the home, away from direct sunlight or other heat
sources that may affect its sensitivity.

Refer to the SignatureStat

t thermostat Installation

Instructions for installation, wiring, and setup. Also refer to
the SignatureStat

t Thermostat Programming Guide for

programming and settings.

To configure the thermostat for operation with a Humidi-
trol

®

system, first enable HUMIDITROL in the thermostat’s

installer settings (follow the path: MENU −> INSTALLER
SETTINGS −> HUMIDITROL − see figure 8, A and B).

Then, select HUMIDITROL mode from the DEHUMIDIFY
menu (follow the path: MENU −> DEHUMIDIFY). The user
control sequence is also shown in figure 8, C through H;
specifically:

S

Turn on Humiditrol − D & E

S

Set level of dehumidification − F through H (adjustment
range is from 45% to 60% and is factory set to 50%)

If HUMIDITROL is enabled and the outdoor sensor is dis-
connected, operation is NOT allowed in dehumidification
mode. This is indicated by the display of "OUTSIDE ERR"
on the SignatureStat

t thermostat Home screen.

Figure 8

Setting Thermostat

INSTALLER SETTINGS

Y

AUTO CHANGEOVER

ON

EER

ON

DEADBAND

4.0°F

HUMIDITROL

OFF

MAIN MENU

SELECT

B

HUMIDITROL

DISABLE

ENABLE

INSTALL MENU

SELECT

MAIN MENU

PROGRAM
HEAT / COOL
HUMIDIFY

DEHUMIDIFY

HOME

SELECT

DEHUMIDIFY MENU

MODE

OFF

DEHUMIDIFY

50%

MAIN MENU

SELECT

DEHUMIDIFY

CONTROL

DEHUM MENU

SELECT

%

50

Installer Setup

User Controls

DEHUMIDIFY MODE

OFF

HUMIDITROL

DEHUM MENU

SELECT

DEHUMIDIFY MENU

MODE

HUMIDITROL

DEHUMIDIFY

50%

MAIN MENU

SELECT

DEHUMIDIFY MENU

MODE

HUMIDITROL

DEHUMIDIFY

55%

MAIN MENU

SELECT

A

B

C

D

E

F

G

H