TABLES

FORCED AIR COOLING (FAC) PERFORMANCE DATA (WITH 30PPI FILTER)

AIRFLOW (w/Filter)

SOUND LEVEL

INPUT POWER (1PH)

FLA / WSA / OPD

MODEL #

# FANS

HIGH

SPEED

LOW

SPEED

HIGH

SPEED

LOW

SPEED

120V/60Hz

220V/50Hz

FAC-190

1

190 CMF

112 CMH

90 CMF

53 CMH

61 dBa

47 dBa

0.5/15/15

0.5/15/15

FAC-360

2

360 CMF

212 CMH

175 CMF

103 CMH

59 dBa

49 dBa

1.0/15/15

1.0/15/15

ENVIRONMENTAL COOLING MODULE (ECM) PERFORMANCE DATA

RATED

CAPACITY

SUPPORT

LOAD

RATED/MAX

AMBIENT

HEIGHT

DIMENSIONS

WIDTH

DEPTH

TOTAL

HEAT REJ.

INPUT POWER (1PH)

WEIGHT

MODEL

NUMBER

BTUH/Watt

BTUH/Watt

60Hz

50Hz

U

In/mm

In/mm

Rack

In/mm

BTUH/Watt

120V/60Hz

220V/50Hz

(lbs/Kg)

ECM-42

4200/1230

2730/800

105F

41C

100F

38C

6

10.5/

265

17.5/

445

19

27/

685

7625/

2235

8/15/15

7/15/15

95/43

ECM-62

6200/1815

4095/1200

105F

41C

100F

38C

7

12.3/

310

22/

560

24

27/

685

11310/

3315

12/20/20

9/15/15

115/52

ECM-80

8000/2345

5800/1700

105F

41C

100F

38C

9

15.8/

400

22/

560

24

29/

735

14605/

4280

16/20/20

16/20/20

167/76

ECM Notes:

Standard Offerings - All Systems

1. 60Hz: R-22 refrigerant / 50Hz: R-134A refrigerant
2. Two-Speed Operation - Switch low-high speed on ambient temperature external to LGH enclosure
3. Automatic Load Matching: Hot gas by-pass factor set for minimum capacity; by-pass will adjust to

match supported loads

4. Condensate Re-evaporation & Removal: Drain connection only required if enclosure seal is violated.