Electrical Service / Connection

The 60 Hz LGH is provided with a single NEMA plug and cord input power connection (except for ECM-
80 systems).

60 Hz Systems with UPS - Service Connection

If a UPS is supplied, the system power rating and plug connection are fixed.

FIXED SERVICE CONNECTION (AMPS)

UPS-GXT (VA)

Cooling
System

1000

1500

2000

FAC-190

15

15

20

FAC-360

15

15

20

UAS/ECM-42

20

--

--

UAS/ECM-62

30

30

--

UAS/ECM-80*

ECM-80 - 20 Amp / UPS-Load - 20 Amp

*LGH ECM-80 systems provided with separate

ECM & UPS power connections.

60 Hz Systems with NO UPS - Service Connection Selection

If a UPS is not supplied, the system power rating and plug connection are customer selected based on
the Cooling System and customer Amp load.

MAX. AVAILABLE CUSTOMER EQUIPMENT AMPS

(based on customer selected Service Connection)

SERVICE CONNECTION

Cooling System

15 Amp

20 Amp

30 Amp

FAC-190

11.5

15.5

23.5

FAC-360

11

15

23

ECM-42 only

--

8

16

UAS-42

--

7

15

ECM-62 only

--

--

12

UAS-62

--

--

10

UAS/ECM-80*

--

--

--

*Power strip is rated for 15 Amp service

50 Hz Systems with NO UPS or WITH UPS - Full Load Amp Draw

The 50 Hz LGH is provided with a cord for input power connection; an appropriate plug is to be field
supplied. Selection charts below are to be used to determine plug requirements per local codes.

FULL LOAD AMP DRAW (230V - 50Hz)

UPS-G (VA)

Cooling System

UPS

1000

1500

2000

FAC-190

.5

4.5

6.5

8.7

FAC-360

1

5

7

9.2

UAS/ECM-42E only

7

11

--

--

UAS/ECM-42E

7.5

11

--

--

UAS/ECM-62E only

9

13

15

--

UAS/ECM-62E

9

13

15

--

UAS/ECM-80E

9

13

15

17

Note: Power strip is rated for 10 Amp service