8 Unpacking and Installation

Figure 3

Typical 25 to 60 Amp SmartSwitch Underfloor / Wallmount Unit

If the unit is furnished with input power cables, the input power connections are made to the

receptacles matching the input power plugs furnished located in close proximity to the Smart-

Switch (typically within 3 feet).
The input power connections to the SmartSwitch must include overcurrent protection included as

part of the supply power distribution system. The maximum supply overcurrent protection for

each SmartSwitch input should not exceed 125% of the rated continuous current or as indicated

on the unit label. The maximum size overcurrent protection device (fuse or circuit breaker) for the

particular SmartSwitch used is listed in the unit ratings table (see Table 1).
The nominal voltage and frequency of each input source must match the voltage rating indicated

on the unit label. Failure to comply with this requirement may result in misoperation or damage

to the unit.
Severe input voltage distortion or large ringing transients, such as those caused by utility capaci-

tor switching, may be interpreted by the SmartSwitch as a source failure.
The SmartSwitch is intended to be supplied from two independent AC power sources to provide

protection against a source failure.