Table 5 example view event log response, Table 6 example view settings response, Table 5 – Liebert SmartSwitchTM User Manual

Page 17: Example view event log response, Table 6, Example view settings response

Advertising
background image

Operating Instructions 13

Table 5

Example View Event Log Response

DATE

TIME

DESCRIPTION

Logged Events include:

10/21/97

16:34:39

Transferred to Preferred

Preferred Source Fail
Preferred Source Available

Alternate Source Fail

Alternate Source Available
Out of Sync

In Sync

Peak Overload
Peak Overload Gone

Transfer Inhibit

OK to Transfer
Power Supply Fault

Power Supply OK

Switch in Normal Mode
Manual Transfer to S1

Manual Transfer to S2

Bypass to S1
Bypass to S2

Transferred to Alternate

Transferred to Preferred
Transfer Test Initiated

Transfer Test Pended

Transfer Test Passed
Transfer Test Failed

10/21/97

16:34:39

Transfer Test Passed

10/21/97

16:34:39

Transferred to Alternate

10/21/97

16:34:38

Transfer Test Initiated

10/21/97

16:34:38

Alternate Source Available

09/27/97

07:22:11

In Sync

09/27/97

07:21:08

Out of Sync

06/01/97

02:10:32

Transferred to Preferred

06/01/97

02:10:29

Preferred Source Available

06/01/97

01:29:13

Transferred to Alternate

06/01/97

01:29:13

Preferred Source Fail

Table 6

Example View Settings Response

CURRENT SETTINGS:
System Time:

10/21/97 16:23:54

Nominal Voltage:

120

Amps:

24

Frequency:

60

Phase:

1

Neutral:

YES

Unit Type:

UNDERFLOOR

Sync Window:

10

Auto Retransfer:

ENABLED

Retransfer Delay:

5

Current Inhibit:

5

Inhibit Type:

MANUAL

Transfer Test:

ENABLED

Next Test:

10/01/97 23:59:58

Test Interval:

90

Preferred Source

S1

Advertising