Table 1 smartswitch™ ratings, Table 1, Smartswitch™ ratings – Liebert SmartSwitchTM User Manual

Page 8

Advertising
background image

4 Introduction

Table 1

SmartSwitch™ Ratings

Connector

Designation

Receptacle

Voltage

No. of Conductors

OPD*

Enclosure

Phase

Neutral

Gnd

Poles

Amps

Type

Refer to

IBMA

3743

208

2

1

2

20

R

Figure 2

IBMB

3744

208

3

1

3

15

U

Figure 3

IBMC

3753

208

2

1

2

30

U

Figure 3

IBMD

3754

208

3

1

3

30

U

Figure 3

IBME

7324

208

3

1

3

60

U

Figure 3

420R9V

420R9V

208

3

1

3

20

U

Figure 3

460R9V

460R9V

208

3

1

3

60

U

Figure 3

515R2

5262

120

1

1

1

1

15

U

Figure 3

515R4

(2) 5262

120

1

1

1

1

15

R

Figure 2

520R2

5362

120

1

1

1

1

20

R

Figure 2

520R4

(2) 5362

120

1

1

1

1

20

R

Figure 2

530R1

9308

120

1

1

1

1

30

U

Figure 3

615R2

5662

208

2

1

2

15

R

Figure 2

620R2

5462

208

2

1

2

20

R

Figure 2

630R1

9330

208

2

1

2

30

U

Figure 3

1420R1

8410

120/208

2

1

1

2

20

U

Figure 3

1430R1

9430

120/208

2

1

1

2

30

U

Figure 3

1520R1

8420

208

3

1

3

20

U

Figure 3

L515R1

4710

120

1

1

1

1

15

R

Figure 2

L520R1

2310

120

1

1

1

1

20

R

Figure 2

L530R1

2610

120

1

1

1

1

30

U

Figure 3

L615R1

4560

208

2

1

2

15

R

Figure 2

L620R1

2320

208

2

1

2

20

R

Figure 2

L630R1

2620

208

2

1

2

30

U

Figure 3

L1420R1

2410

120/208

2

1

1

2

20

U

Figure 3

L1430R1

2710

120/208

2

1

1

2

30

U

Figure 3

L1520R1

2420

208

3

1

3

20

U

Figure 3

L1530R1

2720

208

3

1

3

30

U

Figure 3

L2120R1

2510

120/208

3

1

1

3

20

U

Figure 3

L2130R1

2810

120/208

3

1

1

3

30

U

Figure 3

FW120

None

120

1

1

1

1

20

R

Figure 2

FW130

None

120

1

1

1

1

30

U

Figure 3

FW220

None

208

2

1

2

20

R

Figure 2

FW230

None

208

2

1

2

30

U

Figure 3

FW230N

None

208/120

2

1

1

2

30

U

Figure 3

FW330

None

208

3

1

3

30

U

Figure 3

FW330N

None

208/120

3

1

1

3

30

U

Figure 3

FW360

None

208

3

1

3

60

U

Figure 3

FW113

None

230

1

1

1

1

13

R

Figure 2

FW325N

None

400/230

3

1

1

3

25

U

Figure 3

FW350

None

400

3

1

3

50

U

Figure 3

Consult Factory for other available connectors not shown.
* OPD - Maximum size of Overcurrent Protection Device (fuse or circuit breaker) supplying SmartSwitch.