Combustible Wall Chimney Connector Pass-Throughs

Refer to Figure 9

Method A. 12” (305 mm) Clearance to Combustible Wall Member:

Using a minimum thickness 3.5” (89 mm) brick and a 5/8” (16 mm)

minimum wall thickness clay liner, construct a wall pass-through. The

clay liner must conform to ASTM C315 (Standard Specification for Clay

Fire Linings) or its equivalent. Keep a minimum of 12” (305 mm) of brick

masonry between the clay liner and wall combustibles. The clay liner

shall run from the brick masonry outer surface to the inner surface of

the chimney flue liner but not past the inner surface. Firmly grout or

cement the clay liner in place to the chimney flue liner.

Method B. 9” (229 mm) Clearance to Combustible Wall Member: Using

a 6” (153 mm) inside diameter, listed, factory-built Solid-Pak chimney

section with insulation of 1” (26 mm) or more, build a wall pass-through

with a minimum 9” (229 mm) air space between the outer wall of the

chimney length and wall combustibles. Use sheet metal supports

fastened securely to wall surfaces on all sides, to maintain the 9” (229

mm) air space. When fastening supports to chimney length, do not

penetrate the chimney liner (the inside wall of the Solid-Pak chimney).

The inner end of the Solid-Pak chimney section shall be flush with the

inside of the masonry chimney flue, and sealed with a non-water soluble

refractory cement. Use this cement to also seal to the brick masonry

penetration.

Method C. 6” (153 mm) Clearance to Combustible Wall Member:

Starting with a minimum 24 gage (.024” [.61 mm]) 6” (153 mm) metal

chimney connector, and a minimum 24 gage ventilated wall thimble which

has two air channels of 1” (26 mm) each, construct a wall pass-through.

There shall be a minimum 6” (153 mm) separation area containing

fiberglass insulation, from the outer surface of the wall thimble to wall

combustibles. Support the wall thimble, and cover its opening with a

24-gage minimum sheet metal support. Maintain the 6” (153 mm) space.

There should also be a support sized to fit and hold the metal chimney

connector. See that the supports are fastened securely to wall surfaces

on all sides. Make sure fasteners used to secure the metal chimney

connector do not penetrate chimney flue liner.

Method D. 2” (51 mm) Clearance to Combustible Wall Member: Start

with a solid-pak listed factory built chimney section at least 12” (304 mm)

long, with insulation of 1” (26 mm) or more, and an inside diameter of

8” (2 inches [51 mm] larger than the 6” [153 mm] chimney connector).

Use this as a pass-through for a minimum 24-gage single wall steel

chimney connector. Keep solid-pak section concentric with and spaced

1” (26 mm) off the chimney connector by way of sheet metal support

plates at both ends of chimney section. Cover opening with and sup-

port chimney section on both sides with 24 gage minimum sheet metal

supports. See that the supports are fastened securely to wall surfaces

on all sides. Make sure fasteners used to secure chimney section do

not penetrate chimney flue liner.

1. Connectors to a masonry chimney, excepting method B, shall extend

in one continuous section through the wall pass-through system and

the chimney wall, to but not past the inner flue liner face.

2. A chimney connector shall not pass through an attic or roof space,

closet or similar concealed space, or a floor, or ceiling.

3. Where passage through a wall, or partition of combustible construc-

tion is desired, the installation shall conform to CAN/CSA-B365.

Termination Cap with

Spark Arrestor

Storm

Collar

Flashing

Support

Box

DVL Close Clearance

Connector Pipe

Floor

Protector

3 Feet

Minimum

7 Feet

Minimum

Minimum of

12-15’ of Flue to

achieve a stable

draft.

Double Wall Pipe

(Approved for Model CI2000HT Only)

Using 6” Diameter Type L-Vent Connector Pipe

Figure 8 - Double Wall Pipe