OUTSIDE CONNECTION

Outside

Intake

Screw

Opening

Facing

Down

Wall

Aluminum Tape

Plastic

Cover

Insulation

Flexible Pipe

Aluminum Tape

OUTSIDE AIR

It is mandatory to install an outside air connec-

tion to the Cambria™ fireplace. The following

components are required and are included with

the fireplace:

• Outside air kit

• 4” adapter for fireplace connection

The outside air assembly must be installed ac-

cording to the following requirements:

A) Duct length should be kept to a minimum.

The maximum length of a 4” interior diam-

eter (100 mm) insulated flexible duct is 20

feet (6.1 m). The duct can be extended to a

maximum of 40 feet (12 m) using a 6” interior

diameter (150 mm) insulated flexible duct

(See note below).

B) The air intake register must not be installed

more than 10 feet (3050 mm) above the base

of the fireplace.

C) The fresh air must come from outside the

house. The air intake must not draw air from

the attic, basement or garage.

D) The air intake should be installed where

it is not likely to be blocked by snow or

exposed to extreme wind and away from

automobile exhaust fumes, gas meters and

other vents.

E) The duct and register may be installed above

or below floor level.

Make a 4-1/4” (110 mm) hole in the outside

wall of the house at the chosen location. From

outside, place the outside air register in the hole

(open side down) and fasten the register to the

wall with screws as shown (see Figure 26).

Slip the pipe into the insulated sleeve. Place

the insulated pipe over the register tube and

over the fireplace’s outside air connector (see

Figure 27). At each end, carefully pull back the

insulation and plastic cover exposing the flex-

ible pipe. Using the aluminium tape provided,

wrap the tape around the joint between the

flexible pipe and the air inlets. Carefully push

the insulation and plastic cover back over the

pipe. Using aluminium tape, fasten the plastic

cover in place.

NOTE: We recommend not to exceed 20 feet

(6.1 meters) of 4” flexible pipe. If you require

a longer length we recommend that you use a

5” diameter flexible pipe for the complete run

up to 30 feet and a 6” diameter pipe for a run

of up to 40 feet.

OUTSIDE AIR CONNECTION TO THE FIREPLACE

Figure 26

Figure 27

Fireplace

Fireplace

Connection

Aluminum Tape

Plastic

Cover

Insulation

Flexible Pipe

Aluminum Tape

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.