THE CHIMNEY SYSTEM

Chimney Installation Notes

1. If possible, install an interior chimney as it

will provide better performance. In areas

with continuous temperatures below 0°F

(18°C), the use of an exterior chimney in-

creases the likelihood of operating problems

such as low draft, high rate of creosoting,

and poor start-up characteristics. Exterior

chimneys are also prone to down-drafting

and flow reversal. Installations which are

located on lower floors in the house, such

as in a basement, in combination with an

outside chimney, are especially prone to

flow reversal.

2. The Lennox Hearth Products fireplace model

Cambria™ fireplace is listed only with Se-

curity Chimneys International Ltd 10” dia.

chimney systems model Secure Temp

ASHT+

/ Nova Temp

HT6103+

or AC.

3. A chimney venting a fireplace shall not vent

any other appliance.

4. The minimum chimney height is 15 feet (4.6

m) excluding the fireplace.

5. All chimney installations must include at least

one support in order to be able to take any

lateral load. The maximum chimney length

that can be supported by the fireplace is 12

feet (3.7 m) for Secure Temp

ASHT+

/ Nova

Temp

HT6103+

and 26 feet (8m) for AC chim-

ney. In altitude, add 18” (450 mm) to the

chimney for every 2000 feet (600 m) above

sea level.

6. The chimney must extend at least 3 feet (915

mm) above its point of contact with the roof

and at least 2 feet (610 mm) higher than any

wall, roof or building within 10 feet (3m) of

it (Figure 28).

7. If the chimney extends higher than 5 feet

(1500 mm) above its point of contact with

the roof, it must be secured using a roof

brace.

8. A rain cap must be installed on top of the

chimney. Failure to install a rain cap may

cause corrosion problems.

9. Cut and frame square holes in all floors,

ceilings, and roof that the chimney will go

through to provide a 2” (50 mm) clearance

between the chimney and any combustible

materials. Do not fill this 2” space with

insulation or any other combustible mate-

rial.

10. Portions of the chimney which may extend

through accessible spaces must be enclosed

to avoid contact with combustible materials

or damage the chimney.

Ten (10) Feet

3.1 Meters

Three (3) Feet

.6 Meters

Minimum

Two (2) Feet

.6 Meters

Minimum

CHIMNEY MODEL

SqUARE HOLE

SIZE OPENING

Secure Temp

ASHT+

Nova Temp

HT6103+

16-3/8 in. (416 mm)

AC:

17 in. (432 mm)

Note: See Table 3 for Sloped Roof Framing

Table 2 - Flat Roof Framing

Figure 29 - Roof Framing

CHIMNEY INSTALLATION INSTRUCTIONS

1. Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see Figure

29). Use a plumb-bob to line up the center of the holes. The sizes are indicated in Table 2 for

the floor and ceiling holes and Table 3 (Page 19) for the roof holes.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

17