Caution, Step 4. field wiring, A. millivolt wiring – Lennox International Inc. MERIT PLUS MPB3530CNM-B User Manual

Page 11: Figure 14: sit milivolt wiring diagram

Advertising
background image

11

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS • MERIT PLUS

®

B-VENT GAS FIREPLACES (MPB33/35/40/45) • INSTALLATION INSTRUCTIONS

STEP 4. FIELD WIRING

CAUTION

The ground supply lead must be
connected to the wire attached to
the green ground screw located
on the outlet box (see wiring
diagrams)
. Failure to do so
will result in a potential safety
hazard. The appliance must be
electrically grounded in accor-
dance with local codes or, in
the absence of local codes, the
National Electrical Code, ANSI/
NFPA 70

latest edition (in

Canada, the current CSA C22.1
Canadian Electrical Code).

CAUTION: Label all wires prior to discon-
nection when servicing controls. Wiring
errors can cause improper and dangerous
operation.

ATTENTION: Au moment de l’entretien
des commandes, étiquetez tous les fils
avant de les débrancher. Des erreurs de
cáblage peuvent entraîner un fonc-
tionnement inadéquat et dangereux.

Verify proper operation after servicing.

S’assurer que l’appareil fonctionne adé-
quatement une fois l'entretien terminé.

Refer to Section A for millivolt appliances
and Section B for electronic appliances. The
gas valve is set in place and pre-wired at the
factory on both models.

A. Millivolt Wiring

(see Figure 14)

Millivolt units are not provided with any
factory-installed controls; therefore, one
of the optional control switches is required
to operate the unit (ON/OFF Wall Switch,
Unit-Mountable ON/OFF Switch*, Remote
Control). See the fi replace Care and Operation
Instructions
for details.

[*If using a Unit-Mountable ON/OFF Rocker
Switch with an optional Style View Door,
mount the Rocker Switch on the door instead
of the unit.]

1. If installing an ON/OFF wall switch or

receiver, mount it in a convenient location
on a wall near the f replace.

2. Wire the control switch within the millivolt

control circuit using the 15 feet of 2
conductor wire supplied with the unit.

Note: The supplied 15 feet of 2 conductor wire
has one end of each conductor connected to
the gas valve circuit and the other end of each
conductor placed loose inside the bottom
compartment.

CAUTION

In millivolt systems, do not connect
optional control switch to 120 v power
supply.

B. Electronic Wiring

(see Figure 16)

One of the following optional controls also
may be used: ON/OFF Wall Switch, Remote
Control (see fi replace Care and Operation
Instructions
for details.).

Note: Electronic models must be connected
to the main power supply.

1. Route a 3-wire 120Vac 60Hz 1ph power

supply to the appliance junction box.

2. Remove the electrical inlet cover plate

from the side of the unit by removing the
plate’s securing screws (see Figure 10 on
Page 9).

3. Remove the cover plate knockout; then

feed the power supply wire through
the knockout opening and into the unit
junction box.

4. See Figure 17. Connect the black power

supply wire to the lower outlet’s red
pigtail lead
.

Connect

the

white power supply wire to

the outlet’s common terminal.

5. Connect the ground supply wire to the

pigtail lead attached to the outlet’s green
ground screw.

Note: Remote receiver should be located in the
wall, or if installed in the control compartment,
pulled all the way forward and completely to the
left or right against the corner posts.

Figure 16: Wiring Diagram—Electronic Gas Valves

P/N 580491-01

JUNCTION BOX

120V AC

REMOTE RECEIVER

ON/OFF SWITCH

WALL SWITCH

SAFETY LIMIT SWITCH
B-VENT MODELS ONLY

AC/DC
POWER
ADAPTOR

HOT

NEUTRAL

OPTIONAL

GROUND

BATTERY HOLDER

DFC WIRE HARNESS

SPARK WIRE CABLE

PILOT GROUND WIRE

PILOT
SENSOR
CABLE

HOOD

IGNITER ROD

FLAME SENSOR

PILOT TUBE

CPI

SWITCH

OFF (O) = INTERMITTENT PILOT MODE
ON (-) = STANDING PILOT MODE

PROFLAME DFC BOARD

PROFLAME VALVE

ELECTRONIC PILOT ASSEMBLY

B = BLACK
BR = BROWN
GY = GRAY
PU = PURPLE
R = RED

BL = BLUE
G =

GREEN

O =

ORANGE

W = WHITE
Y = YELLOW

WIRING COLOR CODE

B

B

B

R

R

W

W

B

B

B

B

BL

BL

G

G

O

Y

Y

R

R

Y

W

G

G

O

SCHEMATIC REPRESENTATION ONLY

Figure 14: SIT Milivolt Wiring Diagram

If any of the original wire as supplied must be replaced,
it must be replaced with Type AWM105

° C – 18 GA. wire.

Thermopile

H

T

P

T

H

T

P

T

*TWIST WIRES “ A ” AND “ B ” TOGETHER TO OPERATE UNIT

SOLELY BY MANIPULATING THE GAS VALVE CONTROL KNOB;
OR CONNECT WIRES TO OPTIONAL ON/OFF SWITCH OR WALL

SWITCH OR REMOTE CONTROL RECEIVER TO OPERATE UNIT

*OPTIONAL ON/OFF SWITCH,

WALL SWITCH, OR REMOTE

CONTROL RECEIVER

A

B

H

C

T I

W

S

T I

M I

L

WT

BK

BK

BK

Schematic Representation Only

Figure 15: Optional J-Box/Outlet Box
(Left Side Shown)

See Figure 10 on Page 10
for Optional Electrical Inlet
Knockout Location.

* Field-Provided
Junction Box and
Duplex Receptacle

* Narrow (2-1/8 Inch Wide)
J-Box Required

CAUTION: ENSURE THAT WIRES ARE POSI-
TIONED AWAY FROM HOT SURFACES AND
SHARP EDGES.