Figure 20, Figure 21 – Lennox Hearth C42 User Manual

Page 18

Advertising
background image

18

Flue Restrictors

The flue restrictor settings shown in Figures 22 and 23 are for typical

installations and may need to be adjusted from standard to take into

account other variables in the installation to achieve proper combustion.

See Flue Restrictor Guidelines on this page to assist you in making a

proper flue restrictor adjustment.

The Ravelle™ 42 gas fireplace uses balanced flue technology to ensure

proper combustion. Flue restrictors may need to be installed depending

on the vent configuration of your fireplace. The drawings on Page 19

show all the allowable pipe configurations for the Ravelle 42 gas fireplace.

To properly install the flue restrictor, find your pipe configuration in the

drawings on Page 19 and note which restrictor setting is recommended.

The flue restrictors and four black self-tapping 5/32” allen head screws

can be found in the firebox in a plastic bag. The restrictors should be

placed over the openings at both sides of the ceiling of the firebox. For

each restrictor, two self-tapping 5/32” allen head screws should be in-

stalled in either holes 1, 2, 3, or 4 in the restrictor and screwed into the

two holes in the firebox ceiling. (There are four holes at each side of the

firebox ceiling to receive only two screws. Insert the screws into either

two holes). See the drawing to the right for the location of hole numbers

on the restrictor. The numbered holes in which the screws are inserted

in the restrictor should correspond to the restrictor position numbers

found on the drawings for your pipe configuration. Restrictor positions

are based on tests run in a laboratory. The optimum restrictor positions

may need to be adjusted slightly depending on the conditions surround-

ing the residential installation. Do not adjust restrictors to a point where

the fireplace is sooting.

Notes: The higher the number of the flue restrictor position, the greater

amount of combustion air will be delivered.

Flue Restrictor Adjustment Guidelines

After the flue restrictors have been set to the standard settings as shown

in Figures 22 and 23, the burner flame appearance should be evaluated

to determined if the flue restrictors need to be set to a different position

to adjust for variables in your installation. Light the appliance and allow

it to burn for 20 minutes. See Flame Color and Behavior on Page 30 to

determine if you have a proper burner flame appearance. If the proper

flame appearance cannot be achieved, the flue restrictor may need to be

set to a different position. See the following guidelines to determine if

you need to readjust the flue restrictors.

Before proceeding, confirm the manifold and inlet gas pressure is correct,

primary air shutter is properly adjusted, venting system connections are

secure and not blocked and if you are at a high elevation, ensure unit has

been properly derated:

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more open position.

• Flame appears yellow

• Floating Flames (lazy, ill defined, quiet, may roll)

• Sooting

• Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more closed position.

• Low Flame

• Pilot pulls and appliance shuts down

• Pilot flame ghosts

Termination Heights For Vents

Above Flat Or Sloped Roofs

Ref. NFPA 54 / ANSI Z3.1

Roof Pitch

* Feet

* Meters

Flat to 6/12

1.0

0.3

6/12 to 7/12

1.25

0.38

7/12 to 8/12

1.5

0.46

8/12 to 9/12

2.0

0.61

9/12 to 10/12

2.5

0.76

10/12 to 11/12

3.25

0.99

11/12 to 12/12

4.0

1.22

12/12 to 14/12

5.0

1.52

14/12 to 16/12

6.0

1.83

16/12 to 18/12

7.0

2.13

18/12 to 20/12

7.5

2.29

20/12 to 21/12

8.0

2.44

1

X

Roof Pitch is X/1

 FT

MIN.

 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (5.4 mm) Minimum

Clearance to Combustibles

Vertical Vent Termination Clearances

The vent / air intake termination clearances above the high side of an

angled roof is as shown in the table below.

Figure 20

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 21

Restrictors

Interior of Firebox

Restrictors

Interior of Firebox

Advertising