Lincoln Impinger II - Advantage Series User Manual

Page 14

Advertising
background image

Impinger II – Advantage Service Manual - Domestic

14

Temperature Control

Check for supply voltage at temperature control. If
no voltage is present, trace wiring back to hi-limit
thermostat. Turn the temperature adjustment knob
to maximum temperature position and check for
208/240 VAC at the load terminals 7 and 8. If
208/240 VAC is present and unit is not heating,
refer to "Mercury Contactor" for next check. If
208/240 VAC is not present, proceed.

Thermocouple Probe

WITH POWER ON AND THERMOCOUPLE
LEADS ATTACHED TO THE TEMPERATURE
CONTROL BOARD: measure D.C. millivolt output
of these leads. Refer to thermocouple chart in
Section D for proper readings. If these readings
are not achieved, replace thermocouple.

Temperature

Control

Potentiometer

Disconnect the potentiometer leads from the board.
Place ohm meter test leads on the blue and green
pot. leads. Reading should be 1 K ohms.

Place meter leads across the blue and purple pot.
leads and rotate knob from high to low. Repeat on
green and purple leads. Check for even rise and
fall of ohms reading to insure that there are no open
or dead spots in the potentiometer. Check each
lead to ground for shorts. Replace pot if it does not
meet the above test.

Mercury Contactor

Check for supply voltage to the contactor coil. If
voltage is present and the contactor will not
activate, replace the contactor. Also, check each
contactor for proper high voltage input and output.

Heater Elements

Check the amp draw on each hot leg for proper
load. Check the specifications plate for rating
information. If the amp draw is low or high, check
the individual elements for opens, shorts, and
proper resistance. WITH POWER OFF: To check
resistance of the elements, remove all leads from
the elements and use an accurate digital VOM.
The element resistance should be as follows:
208V - 27 ohms approximately
240V - 36 ohms approximately

Oven heats with switch off

Mercury Contactor

The mercury contactor has probably malfunctioned
in the closed position. If there is no voltage to the
operating coil, but there is high voltage at the
contactor out put, replace the mercury contactor.

Intermittent Heating

Thermal/Overload of motor

The main fan motor is equipped with internal
thermal protection and will cease to operate if
overheating occurs. As the motor overheats and
then cools, this will cause the oven to cycle on and
off intermittently. This may be caused by improper
ventilation or preventive maintenance. Also, most
of the problems listed under "Oven will not heat"
can cause intermittent failure.

Conveyor will not run

Voltage Supply

Check incoming voltage supply at line 1 to neutral.
There should be a voltage reading of 208/240 VAC.
If not present, check breakers.

10 Amp Fuse

Check and/or replace.

Fuseholder

Check and/or replace.

Fan Switch

See procedure for checking on page 8.

Advertising